EasyManua.ls Logo

Lumiax MT2010 - Connection Manual

Lumiax MT2010
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TRACKSO CONNECTION MANUAL FOR LUMIAX CHARGE CONTROLLER
Brand: LUMIAX
Type: Solar Charge Controller
Models: MT2010, MT2075, MT3075BT, MT3010, MT4010, MT4015, MT6020-Pro
CONNECTION DIAGRAM
The communication terminals (RS485) are located at the bottom side of the charge controller
Figure L1 LUMIAX Charge Controller RS485 Port
Connection Steps
1. Create RJ11 wire as per pinout mentioned in photo L1.
2. The charger is equipped with a RS485 port with RJ11 sockets, the
RJ11 interface is defined as mentioned in Figure L1
3. The communication terminals is located at the bottom of the
section as shown in Figure L1
4. Connect the cables to the RS485 bus terminal blocks.
5. Please make the connections from the Terminal Block chip to
TrackSo IoT Gateway as mentioned in the Table TL1
Table-TL1
Controller Pin No.
& Assignment
TrackSo Pin No.
& Assignment
3
A
3
D+
4
B
4
D-
Figure L2 Lumiax RS485 chip connections with TrackSo IoT Gateway

Other manuals for Lumiax MT2010

Related product manuals