5-2
CDA3000 Operation Manual
5  Diagnosis/Fault rectification
5.2 Error messages If a fault occurs in operation it is indicated by a flash code from LED H1
(red) on the inverter module. The code indicates the type of error. If a
KP200 is connected the KP200 indicates the error type as an
abbreviation. 
Helpline If you need further assistance, our specialists at the LUST helpline will be
glad to help.
You can reach us:
Mon.-Thur.: 8 a.m. - 4.30 p.m.Tel. ++49 64 41/9 66-180
Fri.: 8 a.m. - 4 p.m. Tel. ++49 64 41/9 66-180
E-mail: helpline@lust-tec.de
Fax: ++49 64 41/9 66-177
Flash code of 
red LED H1
Display
K
EYPAD 
Explanation Cause/Remedy
1x E-CPU Collective error
Power-off, remove all control signals, power-on. If error recurs, inform LUST 
Service.
1)
2x E-OFF Undervoltage shut-off Check power supply. Also occurs briefly in response to normal power-off.
3x E-OC
Current 
overloadshut-off
Short-circuit, ground fault: Check cabling of connections, check motor 
coil, check neutral conductor and grounding (see also section 3, Installation).
Device setup not correct: Check parameters of control loops. Check ramp 
setting.
4x E-OV
Voltage overload 
shut-off
Voltage overload from mains: Check mains voltage. Restart device.
Voltage overload resulting from feedback from motor
 (regenerative 
operation): Slow down braking ramps. If not possible, use a braking resistor.
5x E-OLM
Motor 
protectionshut-off
Motor overloaded (after I x t monitoring): Slow down process cycle rate if 
possible. Check motor dimensioning.
6x E-OLI
Device safety
shut-off
Device overloaded: Check dimensioning. Possibly use a larger device.
7x E-OTM
Motor temperature
too high
Motor PTC correctly connected?
Parameter MOPTC correctly set(type of motor PTC evaluation)?
Motor overloaded? Allow motor to cool down. Check dimensioning.
8x E-OTI Inverter overheating
Ambient temperature too high: Improve ventilation in switch cabinet.
Load too high during driving/braking: Check dimensioning. Possibly use a 
braking resistor.
1) For more information refer to CDA3000 Application Manual
Table 5.1 Error messages