3-10
CDA3000 Operation Manual
3  Electrical installation
3.7 Control 
terminals
  
Step Action Comment
1
Check whether your inverter module is 
fitted a modified software package 
(Sxx) and/or a ready-to-run data set 
(Dxx).  
If this is the case, the control terminal 
assignment is different. Please con-
tact your project engineer with regard 
to wiring and commissioning!!
Position of software name plate - see 
section 3.1 page 3-2
2
Check whether you already have a 
S
MARTCARD or a  DRIVEMANAGER DATA 
SET with a complete device setup. 
If this is the case, the control terminal 
assignment is different. Please con-
tact your project engineer to obtain 
the terminal assignment!
Bulk customers
For details of how to load the data 
set into the inverter module refer to 
section 4.6.
3
Choose a terminal assignment.
See 3.7.1 "Choice of terminal 
assignment"
4
Wire the control terminals with 
shielded  cables. 
The only essential signals are the 
ENPO signals and a start signal
(STR or STL).
Ground the cable shields over a 
wide area at both ends.
Wire cross-section maximum 
1.5 mm² or two wires per terminal 
with 0.5 mm² 
5
Keep all contacts open 
(inputs inactive).
6
Check all connections again!
Continue with commissioning in 
section 4.
Note the following points: 
• Always wire the control terminals with shielded cables.
• Lay the control cables separately from the mains lead and motor 
cable.
• The CDA3000 Application Manual presents more drive solutions.
ANTRIEBSTECHNIK
D- 35633 Lahnau
Type: CDA32.004,C1.0
Software: V1.10, S xx
C1D1
CS:
D xx
Data Set:
SN.: 99120442