2-2
X6 Des. Control connections
21 UR Ref. voltage 10 V
for ref. pot.
22 FSIN Freq. ref. input
23 Ground Control unit ref. point
24 STR Start clockwise input
25 STL Start counter-clockwise
input
26 UV Control voltage 24 V DC
29 SOUTF Digital freq. output
33 S1IND Prog. digital input
34 S2IND Prog. digital input
35 S3IND Prog. digital input
36 SOUTA Prog. analog output
41 S1OUT Break contact of relay 1
42 Cent. spring of relay 1
43 Make contact of relay 1
44 S2OUT Break contact of relay 2
45 Cent. spring of relay 2
46 Make contact of relay 2
K1 Example of mains protection
connection
Y
Example of connection for ext.
mains filter
ground line
X EMC ground clamps for easy
installation
of cable screen
VF1404M
VF1406M
VF1408M
VF1410M
wait 2 minutes
after mains off
X1 Power connections
L1,L2,L3 Mains connection 3 x 400/460 V
U,V,W Motor connection 3 x 400/460 V
X2/ + , - Connection for DC-link coupling
X2/ RB Connection for ext. braking resistor
X3 Socket for
control unit KEYPAD KP100
X4/51, 52 Motor PTC connection
1)
X5/ Connection terminal for
47,48,49,50 interface RS485
1)
or RS232
1)
1) Terminal assignment depends on design ordered
Attention:
Starting torque
of terminal X1
and X2
max. 0,4-0,5 Nm
-
RB RB +
41
42
43
44
45
46
n.c.
23
29
36
21
22
23
24
25
26
33
34
35
26
47
48
49
50
51
5
2
-
+
SOUTA
S2OUT
S1OUT
SOUTF
FSIN
UR
+24V
+10V
STR
STL
S1IND
S2IND
S3IND
V
DD
GND
A
B
RS485
1)
RB1
1)
W V U L3
L2
L1
M
3
K1
SI
L1
L2
L3
PE
3 x 400/460VAC
SI
SI
KP100
PTC
1)
U
V
X6/1
X6/2
X5
X4
X3
X2
X1
X
001
Y
X