5-3
Operating level 2 (Part 2)
Abbrev. Name Unit Setting range Page Factory Customer
setting
Special functions
48-IXR I∗R compensation - 0 to 3 6-11 0
49-SC Slip compensation - 0 to 2 6-13 0
50-IN Motor rated current A 0 to 150% I
Rated
6-13 *
51-COS Power factor x100 % 0 to 100 6-13 82
52-NN Motor rated speed UPM 0 to 24000 6-13 1400 (1700**)
53-KIXR Correction factor of the - 0 to 30 6-14 *
I∗R compensation
54-KSC Correction factor of - 0.0 to 30.0 6-14 5
slip compensation
55-ISEL Current control-selector - 0 to 2 6-14 0
56-ILIM Current limit A 25 to 150% I
N
6-16 *
57-FILIM Min. sink frequency Hz 0.0 to 999.0 6-16 15
58-RILIM Delay ramp Hz/s 0.1 to 999.0 6-16 50
for current control
59-TRIP I∗t monitoring A 25 to 150% I
N
6-16 *
Signal outputs
61-SOUTA Frequency-/analog- - 0 to 14 6-17 9
output
62-S1OUT Output 1 digital - 0 to10 6-18 10
63-S2OUT Output 2 digital - 0 to10 6-18 7
67-FST Filter time constants - 0 to 4 6-18 2
69-KOUTA SOUTA scaling % 0 to 200 6-19 100
Program -functions
71-PROG Special programs - 0 to 4 6-19 0
72-STRT Start options - 0 to 7 6-19 0
74-PWM Modulation frequency - 0 to 2 6-20 0
75-OPT1 Option 1*** - 0. 2 or 4 6-20 0
86-KG Scaling factor - 0 to 200 6-21 0
for 10-G
87-DISP Saved long-term - All display 6-21 12-F
Actual value display - parameters
88-PSW1 Pass word1 <PARA> - 0.0 to 999.0 6-21 0
89-PSW2 Pass word 2 <CTRL> - 0.0 to 999.0 6-21 573
94-MAXF Absolute max. frequency Hz 4.0 to 999.0 6-22 0
*Depends on inverter type, **Factory setting B (see 5-4)
***Caution: This parameter can only be modified in operating mode 01-MODE = 3.
Note: I
N
=> device rated current (see type plate)
U
N
=> device rated voltage (see type plate)