EasyManua.ls Logo

Lust SMARTDRIVE VF1000 M Series - Operating Level 2 Parameters

Default Icon
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-2
5.2 Operating level 2
Abbrev. Name Unit Setting range Page Factory Customer
setting
Reference input
4-FSSEL Frequency ref. selector - 0 to 23 6-1 0
Actual values
9-BARG Bar graph assignment - 6 Actual values 6-5 13-V
Frequencies
20-FF2-1 1st Fixed frequency 2 Hz 0.0 to 999.0 6-7 3
21-FMIN1 1st Minimum frequency Hz 0.0 to 999.0 6-7 0
22-FMAX1 1st Maximum frequency Hz 4.0 to 999.0 6-7 50
23-FF3 Fixed frequency 3 Hz 0.0 to 999.0 6-7 15
24-FF4 Fixed frequency 4 Hz 0.0 to 999.0 6-7 30
25-FF5 Comparative frequency Hz 0.0 to 999.0 6-7 3
for S2OUT
26-FF6 Control frequency Hz 0.0 to 999.0 6-7 0
(Data set)
27-FF2-2 2nd Fixed frequency 2 Hz 0.0 to 999.0 6-7 5
28-FMIN2 2nd Minimum frequency Hz 0.0 to 999.0 6-7 0
29-FMAX2 2nd Maximum frequency Hz 4.0 to 999.0 6-7 50
30-FF7 Fixed frequency FF7 Hz 0.0 to 999.0 6-7 50
Ramps
31-KSEL Data set selector - 0 to 3 6-8 0
32-RACC1 1st acceleration ramp Hz/s 0.1 to 999.0 6-9 20
33-RDEC1 1st delay ramp Hz/s 0.1 to 999.0 6-9 20
34-RACC2 2nd acceleration ramp Hz/s 0.1 to 999.0 6-9 80
35-RDEC2 2nd delay ramp Hz/s 0.1 to 999.0 6-9 80
36-RSTOP STOP-delay ramp Hz/s 0.0 to 999.0 6-9 0
Characteristics
38-THTDC Shut-down delay s 0.0 to 120.0 6-10 0
39-VHTDC DC retaining voltage % 1 to 25 6-10 4
41-V/FC V/F characteristics selector - 1 and 4 6-10 1
42-VB1 Starting voltage (Boost 1) % 0.0 to 25.0 6-10 8
43-FN1 Frequency-rated point 1 Hz 15.0 to 960.0 6-10 50/60**
44-VN1 Voltage-rated point 1 V 43%...119% U
N
6-10 *
45-VB2 Starting voltage (Boost 2) % 0.0 to 25.0 6-10 *
46-FN2 Frequency rated point 2 Hz 15.0 to 960.0 6-11 50/60**
47-VN2 Voltage rated point 2 V 43%...119% U
N
6-11 *
*Depends on inverter type, **Factory setting B
Note: When setting parameter 71-PROG to 1, all programmable
parameters are set to the factory setting on confirmation of
the parameter modification by pressing on the start/enter key
(Message "wait").

Related product manuals