EasyManua.ls Logo

Lust SMARTDRIVE VF1000 M Series - Electrical Connections; Connection Plan

Default Icon
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-1
2 Electrical Connections
2.1 Connection plan
wait 2 minutes
after mains off
VF1205M
VF1207M
K1 Example of mains protection
connection
Y
Example of connection for ext.
mains filter
Ground line
X EMC ground clamps for easy
installation of cable screen
X1 Power connections
L1,N, Mains connection 1 x 230 V
U,V,W Motor connection 3 x 230 V
X2/ + , - Connection for DC-link coupling
X2/ RB Connection for ext. braking resistor
X3 Socket for
control unit KEYPAD KP100
X4/51, 52 Motor PTC connection
1)
X5/ Connection terminal for
47,48,49,50 interface RS485
1)
or RS232
1)
X6 Des. Control connections
21 UR Ref. voltage 10 V
for ref. pot.
22 FSIN Freq. ref. input
23 Ground Control unit ref. point
24 STR Start clockwise input
25 STL Start counter-clockwise input
26 UV Control voltage 24 V DC
29 SOUTF Digital freq. output
33 S1IND Prog. digital input
34 S2IND Prog. digital input
35 S3IND Prog. digital input
36 SOUTA Prog. analog output
41 S1OUT Break contact of relay 1
42 Cent. spring of relay 1
43 Make contact of relay 1
44 S2OUT Break contact of relay 2
45 Cent. spring of relay 2
46 Make contact of relay 2
1) Terminal assignment depends on design ordered
Attention:
Starting torque
of terminal X1
and X2
max. 0,4-0,5 Nm
-
RB RB +
41
42
43
44
45
46
n.c.
23
29
36
21
22
23
24
25
26
33
34
35
26
47
48
49
50
51
52
-
+
SOUTA
S2OUT
S1OUT
SOUTF
FSIN
UR
+24V
+10V
STR
STL
S1IND
S2IND
S3IND
V
DD
GND
A
B
RS485
1)
RB1
1)
KP100
PTC
1)
U
V
X6
X6
X5
X4
X3
X2
X1
001
W V U
N
L1
M
3
K1
SI
L1
N
PE
1 x 230VAC
Y
X
X

Related product manuals