EasyManua.ls Logo

Lust SMARTDRIVE VF1000 M Series - Page 58

Default Icon
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-3
04-FSSEL = 0
FSIN is active as analog input. The adaption to 0(2) ... 10 V or
0 (4) ... 20 mA is via jumper rail J1 ... J6.
04-FSSEL = 1, 2
Without function.
04-FSSEL = 3
FSIN functions as frequency input.
FMIN = 0 Hz FMAX = 1 kHz, adaption via jumper rail J1 ... J6.
04-FSSEL = 4
FSIN functions as frequency input.
FMIN = 0 Hz FMAX = 10 kHz, adaption via jumper rail J1 ... J6.
04-FSSEL = 5
FSIN operates as clock input for impulse width modulated signal.
FMIN = 20% PWM FMAX = 100% PWM (see Fig. 6-2). The basic
signal of the PWM signal must be 0.9 ... 8 kHz, adaption via J1 ... J6.
04-FSSEL = 6
FSIN operates as clock input for impulse width modulated signals.
FMIN = 0% PWM FMAX = 100% PWM (see Fig. 6-2). The basic
frequency of the PWM signal must be 0.9 ... 8 kHz, adaption via
jumper rail J1 ... J6..
0
U/V
t
10
tp
T
Fig. 6-2
04-FSSEL Adjustment range A
5 0 ...100% PWM 0
6 20...100% PWM 0,2
FSIN Hz
FMAX FMIN
A
KA FMIN[]
()
()=
⋅−+
1
K
t
T
P
=

Related product manuals