6-3
04-FSSEL = 0
FSIN is active as analog input. The adaption to 0(2) ... 10 V or
0 (4) ... 20 mA is via jumper rail J1 ... J6.
04-FSSEL = 1, 2
Without function.
04-FSSEL = 3
FSIN functions as frequency input.
FMIN = 0 Hz FMAX = 1 kHz, adaption via jumper rail J1 ... J6.
04-FSSEL = 4
FSIN functions as frequency input.
FMIN = 0 Hz FMAX = 10 kHz, adaption via jumper rail J1 ... J6.
04-FSSEL = 5
FSIN operates as clock input for impulse width modulated signal.
FMIN = 20% PWM FMAX = 100% PWM (see Fig.  6-2). The basic
signal of the PWM signal must be 0.9 ... 8 kHz, adaption via J1 ... J6.
04-FSSEL = 6
FSIN operates as clock input for impulse width modulated signals.
FMIN = 0% PWM FMAX = 100% PWM  (see Fig. 6-2). The basic
frequency of the PWM signal must be 0.9 ... 8 kHz, adaption via
jumper rail J1 ... J6..
0
U/V
t
10
tp
T
Fig. 6-2
04-FSSEL Adjustment  range A
5 0  ...100% PWM 0
6 20...100% PWM 0,2
FSIN Hz
FMAX FMIN
A
KA FMIN[]
()
()=
−
−
⋅−+
1
K
t
T
P
=