Energi Savr NodeTM QS | Programming Guide
Energi Savr NodeTM QS
|
Programming Guide Lutron®
|
4
Please refer to the daylight sensor installation guide for details on sensor placement.
Infrared (IR) Remote Receivers
Energi Savr Node QS units are programmable to turn lights on and off based on signals provided by
compatible Lutron® IR transmitters and received by compatible Lutron IR receivers. To ensure proper operation
of the Energi Savr Node QS unit:
• UseonlyLutronIRreceivers(EC-DIR-WH,EC-IR-WH,CC-1BRL-WH,CC-4BRL-WH)
• SeeLutron IR receiver literature for compatible IR transmitters.
• OnlywireonereceivertoasingleIRinput
Advanced Button Programming
Each Energi Savr Node QSunitzonehasseveralparametersthatcanbesetoradjusted.Followthesteps
belowtoadjustazone’ssetting.
Configure Zone Parameters
1. Simultaneously press and hold the Program and Inputbuttonsfor3secondstoenterZoneSet-upMode.
‘Program’andGroupALEDswillashrapidly.
2. Press Zonebuttontoselectthezoneforwhichyouwishtosetparameters.
3.UsetheOptionbuttontoselectaparametertosetoradjustaslistedbelow.TheoptionLEDswillturnonto
indicate your selection:
Option LED(s) Parameter Method
‘Def’
SetzonetorespondtowiredOccupancy
sensor as either Occupancy or Vacancy
sensor
Usethe and buttons to select response mode.
·‘H’LEDindicatesOccupancymode(Autoon/off).
·‘M’LEDindicatesVacancymode(Manualon/
auto off)
‘Opt1’
Set daylight sensor setpoint for each
zone
Usethe button to increase the set point.
Usethe button to decrease the set point.
4.Repeatsteps2and3foreachdesiredzone.
5. Simultaneously press and hold the Program and Inputbuttonsfor3secondstoexitZoneSet-upMode.
Scene Programming Mode
Scene Programming
EachoutputzoneontheEnergi Savr Node QS unit has 16 scenes plus Off. Each scene can be programmed
toturnthezoneonoroff,orthezonecanbesettobeunaffectedinascene,sothatchangingtothatscene
willnotchangetheunaffectedzonefromitscurrentlevel.Note:SceneOffcannotbemodied.
Follow the steps below and in the QS Link Input(s) Set-up section.
Scenes 1-4
1. Simultaneously press and hold the Program and Option buttons on the Energi Savr Node QS unit for 3
secondstoenterSceneProgrammingMode.‘Program’andGroupBLEDswillashrapidly.
2.UsetheOptionbuttontoselectascenetodeneforeachzone.OptionLEDwillbesteadyon,toindicate
current scene selected:
LED Legend: = steady on = flashing = off
LEDs Scene # LEDs Scene # LEDs Scene # LEDs Scene #
Scene 1 Scene 2 Scene 3 Scene 4
3.Usethe and buttonstosettheselectedscenetoOnorOff.The‘H’,‘M’,and‘L’LEDgroupindicatesyour
choice: all LEDs on = On; all LEDs off = Off.
4.Tomakeazoneunaffected,pressandholdthe buttonuntilonlythe‘M’LEDturnson.