Loading...
Energi Savr NodeTM QS | Programming Guide
Energi Savr NodeTM QS
|
Programming Guide Lutron®
|
7
QSE-IO Association - Scene DIP configuration
The Energi Savr Node QS unit can be associated to a QSE-IO (contact closure interface) that is set in a Scene
DIP configuration. This can be used to change scenes on your Energi Savr Node QS unit from third party
equipment(usingcontactclosureinputsintotheQSE-IO),ortomonitorscenechangesonyourEnergi Savr
Node QS unit from third party equipment (using contact closure outputs out of the QSE-IO). Consult the QSE-
IO instructions for proper DIP configuration.
To associate a QSE-IO that is set in a Scene DIP configuration to an Energi Savr NodeQSunit(s),followthe
steps below:
1. Press and hold the Program button on the QSE-IO for 3 seconds to enter Programming Mode. The 5 output
LEDswillcycle.ThesensorGroupAandGroupBLEDsandthe‘H’,‘M’and‘L’LEDsontheEnergi Savr Node
QSunit(s)willashsequentiallyingroups.
2.Toassigndesiredzone(s)totheQSE-IO,pressandholdtheZone button on the Energi Savr Node QS unit for
eachdesiredzonefor3seconds.Ablinking‘Zone’LEDindicatesanassignedzone.
3.ToexitProgrammingMode,pressandholdtheProgram button on the QSE-IO for 3 seconds.
Toun-assignzonesfromtheQSE-IO,pressandholdtheZone button on the Energi Savr Node QS unit for 3
seconds.The‘Zone’LEDwillturnofftoindicatesuccess.
Repeatforeachzonethatyouwishtoun-assignfromtheQSE-IO.
QSE-IO Association - Zone Toggle and Occupancy DIP configurations
The Energi Savr Node QS unit can also associated to a QSE-IO (contact closure interface) that is set in the
ZoneToggleorOccupancyDIPconguration.IntheZoneToggleconguration,thiscanbeusedtotoggle
zonesonyourEnergi Savr Node QS unit from third party equipment (using contact closure inputs into the
QSE-IO),ortomonitorthestate(onoroff)ofthezonesonyourEnergi Savr Node QS unit from third party
equipment(usingcontactclosureoutputsoutoftheQSE-IO).IntheOccupancyconguration,thiscanbe
usedtoassociateadditionaloccupancysensorstothezonesonyourEnergi Savr Node QS unit (to turn lights
on and off based on room occupancy). Consult the QSE-IO instructions for proper DIP configuration.
ToassociateaQSE-IOthatissetinaZoneToggleorOccupancyDIPcongurationtoanEnergi Savr Node QS
unit(s),followthestepsbelow:
1. Press and hold the Program button on the QSE-IO for 3 seconds to enter Programming Mode. The first
outputLEDwillashindicatinginput1isselected.ThesensorGroupAandGroupBLEDsandthe‘H’,‘M’
and‘L’LEDsontheEnergi Savr NodeQSunit(s)willashsequentiallyingroups.
2.Toassigndesiredzone(s)toinput1oftheQSE-IO,pressandholdtheZone button on the Energi Savr Node
QSunitforeachdesiredzonefor3seconds.Ablinking‘Zone’LEDindicatesanassignedzone.
3. Press and release the Program button on the QSE-IO to select the next input. Repeat step 2 for the remaining
inputs on the QSE-IO.
4.ToexitProgrammingMode,pressandholdtheProgram button on the QSE-IO for 3 seconds.
Toun-assignzonesfromtheQSE-IOinputs,pressandholdtheZone button on the Energi Savr Node QS unit
for3seconds.The‘Zone’LEDwillturnofftoindicatesuccess.
Repeatforeachzonethatyouwishtoun-assignfromitsrespectiveQSE-IOinput.

Related product manuals