6 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 4 Operation Manual 90-30027-00 Rev A-01 Date: 032720
Network Wiring Requirements:
Use stranded CAT5e or higher shielded cable.
Minimum 24AWH (0.5mm) cross section.
Ground the shielding and drain wire at only one point of the cable run.
Route wires as far away as possible from high voltage AC cables, fluorescent lights, arc
welders, and other equipment that transmits EMI (electromagnetic interference).
Do not run CAT5e in conduit with high voltage AC cables.
Do not exceed 400ft [122m] of CAT5e between each fan in the network.
Daisy Chain
Network MacroAir fans must be connected in one single line, referred to in this document as a
“daisy chain”. The characteristics of a proper daisy chain are: one beginning (Controller 4) and
one end (last fan or control panel).
If the fans are not connected in
one line/chain, there will be a
degradation of the communication
signal and the network may not
function as intended (fans in the
network may not operate).
Each fan has a unique address,
which is noted on a sticker on the
fan itself (AVD 370) or control
panel (AVD3, 550, 780, Y and X
Series Fans). It is important to
mount the fans in the correct
order.