6 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 4 Operation Manual 90-30027-00 Rev A-01 Date: 032720
Network Wiring Requirements:
• Use stranded CAT5e or higher shielded cable.
• Minimum 24AWH (0.5mm) cross section.
• Ground the shielding and drain wire at only one point of the cable run.
• Route wires as far away as possible from high voltage AC cables, fluorescent lights, arc
welders, and other equipment that transmits EMI (electromagnetic interference).
• Do not run CAT5e in conduit with high voltage AC cables.
• Do not exceed 400ft [122m] of CAT5e between each fan in the network.
Daisy Chain
Network MacroAir fans must be connected in one single line, referred to in this document as a
“daisy chain”. The characteristics of a proper daisy chain are: one beginning (Controller 4) and
one end (last fan or control panel).
If the fans are not connected in
one line/chain, there will be a
degradation of the communication
signal and the network may not
function as intended (fans in the
network may not operate).
Each fan has a unique address,
which is noted on a sticker on the
fan itself (AVD 370) or control
panel (AVD3, 550, 780, Y and X
Series Fans). It is important to
mount the fans in the correct
order.