OPERATION AND MAINTENANCE MANUAL
THREE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.6 03/08/2010 Doc: MAN-3P_MCRII_REV1.6.Doc Page 16 of 29
Magellan Powertronics
68 Cocos Drive, Bibra Lake, WA 6136 Tel: 08 94346621 Fax: 08 94346623
In order to perform constant current charging, it is necessary to ensure no load is connected to
the charger (due to the high output voltage). The system has built in protection that will
terminate the constant current mode if any load current is detected.
Select the Constant Current Setting menu. (See User Adjustable Set Point Instructions. A
warning screen will appear informing the user to ensure the load is disconnected. Press the
Mode key on the rectifier front panel to clear the warning.
Set the Constant Current Mode to ON by using the Arrow keys.
Pressing the Mode key will display the period which the charger will operate in Constant
Current Mode. Adjust by using the Arrow keys (if necessary.)
Pressing the Mode key will now display the charging rate at which the charger will operate
while in constant current mode. Adjust by using the Arrow keys (if necessary).
Pressing the battery test key will initiate constant current mode. The charger will remain in
this mode until the preset time has elapsed. The charger will then return to its normal state.
Constant current charging can be manually terminated by operating the Reset key.
Remote Communications (Optional)
The charger can communicate to an external or remote computer or LAN via an optional
communication card. The communication methods available are:
RS-232, DB-9
RS-485
Ethernet RJ-45
All information relating to the communications port is located in the MCRII Remote
Communications Manual supplied with the MCRII Remote Communications Package.