7.0 COMMISSIONING
7.1 Start-Up
Before delivery the charger is factory adjusted in accordance with the test sheets. The actual
Setpoints loaded are recorded in the Downloaded System Setpoints in Appendix-2.
The factory settings for float and boost rate charge volts are calculated to correspond with the
number and type of battery cells.
Note:
Before testing the systems functions, the Commissioning Personnel should be familiar
with the factory setting of each set point, including alarm delays and latching functions.
Check that the mains supply matches the supply requirements stated on the Ratings plate.
Connect the mains power. Follow the start up procedure.
7.2 Checking Voltage Levels
Before making any adjustments and to obtain the correct set points of the charger, consult the
Downloaded System Setpoints in Appendix-2. Ensure the battery is fully charged, this
prevents unnecessary waiting time for the voltage to reach the boost level. When checking the
voltage, check that the charger does not operate in current limit or without load. A good rule
is to use a load current of between 5 and 80% of the nominal rated current.
7.3 Checking Float voltage
With the charger set to float, connect a precision voltmeter across the Charger Output
terminals X2 and take a reading.
If adjustment is required refer to the Adjustments section.
Note:
With zero current the charger output voltage may be slightly different from the
set Float voltage. Please take the readings with at least 5% load on the charger.