OPERATION AND MAINTENANCE MANUAL
THREE PHASE MCRII SERIES BATTERY CHARGER
Rev: 1.6 03/08/2010 Doc: MAN-3P_MCRII_REV1.6.Doc Page 20 of 29
Magellan Powertronics
68 Cocos Drive, Bibra Lake, WA 6136 Tel: 08 94346621 Fax: 08 94346623
function
Boost Inhibit Enables a total inhibit of boost mode operation
Load Sense Boost Inhibit Disables the boost function if a load is connected
Battery Connection Pulse inhibit Inhibits pulsing the battery to find out if it is
connected to the system.
Muted-Alarm Trip Sets the operational mode of the Mute key (see
Operating Instructions)
Impedance Monitoring Enables the Impedance Monitoring option.
Mains Fail O/P Latch On/Off Sets the mains fail alarm output to latching
Earth Fault O/P Latch On/Off Sets the earth fault alarm output to latching
Low Electrolyte O/P Latch On/Off Sets the Low Electrolyte alarm output to latching
Battery Discon. O/P Latch On/Off Sets the battery disconnected alarm output to latching.
DC High O/P Latch On/Off Sets the DC High alarm output to latching
DC Low O/P Latch On/Off Sets the DC Low alarm output to latching
Charger Fail O/P Latch On/Off Sets the charger fail alarm output to latching
Battery Fail O/P Latch On/Off Sets the battery fail alarm output to latching
Sub Menu 6 Constant Current Charging Set up
(This feature is optional.)
The following set points are used to select and set the parameters for constant current battery
charging.
Constant Current Charging on/off Enables constant current charging cycle to be
activated.
Constant Current Time Sets the period in which the charger will remain in
constant current mode.
Constant Current Rate Sets the constant current level