Sub Menu 7 Charger and Battery Definition Set up
Note: This menu is password protected. Adjustment should only be made in consultation with
Magellan Powertronics.
The following set points are used to set the MCRII Controller to match the charger hardware
(Charger and battery size and type).
Serial Number Serial Number of the Charger
Model Voltage Identifies the charger nominal output voltage
Model Current Identifies the charger maximum output current
Charger ID No Identifies the charger for serial communications
purposes when more than one charger is connected to
the remote communication facility.
Dual Battery Enabled Dual or Single Battery operation
Battery Type Sets the type of battery to be charged by the charger.
(Ni-cad, sealed or vented lead acid)
Temperature Compensation Factor
Sets the temperature compensation in mV/°C/Cell
No of cells Sets the No of cells to be used in the battery bank
Battery 1 Size Sets the ampere hour capacity of the Battery bank 1.
Battery 2 Size Sets the ampere hour capacity of the Battery bank 2.
New Security Code The new value of the security code
Sub Menu 8 Calibration
Note: This menu is password protected. Adjustment should only be made in consultation with
Magellan Powertronics.
The chargers are factory calibrated and the calibration should not normally be changed.
Automatic calibration is available with the Charger Monitoring Software.
The following set points are used to calibrate the LCD metering functions and the charger
voltage control output. Follow the procedure given below to calibrate the metering using the
LCD and Keypad.
To calibrate each setting it is necessary to connect a calibrated meter in circuit to measure the
required meter function. The set point should then be adjusted by the front panel arrow keys
so the set point equals the external calibrated meter measurement. All set points, with the
exception of the Reference Voltage O/P Calibration set point, can be adjusted up or down by
the front panel arrow keys.