48-651 SIL Certified Safety Manual for E3 Modulevel
®
6.2 Installation
Refer to the E3 MODULEVEL Installation and Operating
Manual 48-635 manual for complete installation instruc-
tions.
• Contains information on the use, changing and resetting of
the password-protection function.
• Provides menu selection items for configuration of the
transmitter as a level sensing device.
• Offers configuration recommendations.
• Input voltage and loop resistance must be within the safe
operating area of the device.
6.3 Skill Level of Personnel
Personnel following the procedures of this safety manual
should have technical expertise equal to or greater than that
of a qualified Instrument Technician.
6.4 Necessary Tools
No special equipment or tools are required to install
E3 MODULEVEL. The following items are recommended:
• Wrenches, flange gaskets, and flange bolting
appropriate for process connection(s)
• Flat-blade screwdriver
• Level
•
1
⁄8" Allen wrench
• 24 VDC power supply, 23 mA minimum
• Digital multimeter
• 250 to 450 ohm resistor for HART communication
6.5 Configuration Information
6.5.1 General
The E3 MODULEVEL can be configured via the local dis-
play, the HART compatible handheld communicator, or a
PC using PACTware and associated DTM.
6.5.2 Configuration
Ensure the E3 MODULEVEL transmitter has been proper-
ly configured for the application. Special consideration
should be given to the following configuration parameters:
User Password: Must be changed to a specific value other
than Zero.
Failure Alarm: DO NOT choose HOLD for this parameter
as a Fault will not be annunciated on the current loop.