Guided Wave Radar
Level Transmitter
Enhanced Model 705
Software v3.x
Installation and Operating Manual
2014/68/EU

Table of Contents

Other manuals for Magnetrol eclipse 705

Questions and Answers

  • J
    Jennifer RojasSep 12, 2025
    What to do if LEVEL reading is correct but LOOP is stuck at 4 mA on Magnetrol Transmitter?
    • B
      Betty JonesSep 12, 2025
      If the LEVEL reading on the Display is correct, but the LOOP is stuck on 4 mA, the basic configuration data might be questionable. Set the POLL ADR to 0 if you are not using HART multi-drop.
  • A
    Anthony KeithAug 25, 2025
    Why are LEVEL readings on Magnetrol Measuring Instruments consistently inaccurate?
    • D
      Daniel VillanuevaAug 25, 2025
      If LEVEL readings are consistently high or low by a fixed amount, the configuration data might not accurately match the probe length or tank height. Ensure the proper Probe Model, Level Offset, or probe length is configured. You can also adjust the trim level value by the amount of noted inaccuracy.
  • J
    Jill BakerAug 25, 2025
    What to do if the LEVEL reading is stuck at full scale on Magnetrol eclipse 705?
    • L
      leslie71Aug 26, 2025
      If the LEVEL reading on the display is stuck at full scale, the software might believe the probe is flooded. Check the actual level. If the probe isn't flooded, inspect for buildup or obstructions near the top of the probe. You may also select a higher dielectric range, check for condensation in the probe connection, or add Blocking Distance.
  • M
    martinlatoyaSep 23, 2025
    What does 'LVL < Probe Length' mean on Magnetrol Transmitter?
    • C
      Crystal SullivanSep 23, 2025
      If 'LVL < Probe Length', the apparent position of the upper level pulse is beyond the end of the probe. Check the entered probe length and change the threshold to fixed.
  • J
    James SalasSep 12, 2025
    What does it mean when EOP is less than probe length on Magnetrol Transmitter?
    • K
      Kara BrownSep 12, 2025
      If the EOP (End of Probe) is less than the Probe Length, the End of Probe signal from a dry probe is out of range. Ensure the probe length is entered correctly. Also, set the transmitter to a lower dielectric range and ensure proper blocking distance.
  • V
    Vickie BaileySep 18, 2025
    What does 'FidShift' mean on Magnetrol Transmitter and how can I resolve it?
    • M
      Mr. John Jones Jr.Sep 18, 2025
      If you see 'FidShift', it means the FidTicks have shifted from the expected value. Check the connection between the probe and the transmitter, check for moisture on top of the probe, and check for a damaged gold pin on the high-frequency connector.
  • J
    judy91Sep 5, 2025
    How to resolve 'Lo Temperature' warning on Magnetrol eclipse 705 Measuring Instruments?
    • R
      Rebecca CoxSep 5, 2025
      If the present temperature in the electronics compartment is below -40°F (-40°C), the transmitter may need to be moved to ensure the ambient temperature is within specification, or change to a remote transmitter.
  • L
    Lisa AndersonSep 6, 2025
    How to fix inaccurate LEVEL, % OUTPUT, and LOOP values on Magnetrol Transmitter?
    • A
      Andrew AlvaradoSep 6, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all inaccurate, the basic configuration data might be questionable. Try reconfiguring the Probe Model, Probe Mount, Probe Length, or Level Offset. Also, ensure the Level is accurate and verify the 4 mA and 20 mA Loop values.
  • B
    Bruce KramerSep 18, 2025
    What does 'Fid Sprd' mean on Magnetrol Transmitter, and what steps should I take to correct it?
    • P
      paul10Sep 18, 2025
      If you see 'Fid Sprd', it means the Fiducial Ticks variation is excessive. Check the connection between the probe and the transmitter and check for moisture on top of the probe.
  • E
    Emily McguireAug 30, 2025
    Why is the LEVEL value reading high when it should be zero on Magnetrol eclipse 705 Measuring Instruments?
    • L
      Lisa HarrisAug 30, 2025
      If the LEVEL value is reading high when it should be zero, the transmitter might be loose or disconnected from the probe. Ensure the transmitter is securely connected to the probe.

Summary

QuickStart Installation

Getting Started

Prerequisites and initial steps for installation.

QuickStart Mounting

Procedures for mounting the transmitter and probe.

QuickStart Wiring

Steps for making electrical connections.

QuickStart Configuration

Basic setup and configuration of the transmitter.

Complete Installation

Unpacking

Procedures for safely unpacking the instrument.

Electrostatic Discharge (ESD) Handling Procedure

Safety guidelines for handling sensitive electronic components.

Before You Begin

Preparatory checks and considerations before installation.

Mounting

Details on probe and transmitter mounting procedures.

Installing a Coaxial Probe

Specific steps for installing coaxial probes.

Installing a Twin Rod Probe

Specific steps for installing twin rod probes.

Installing a Single Rod Probe

Specific steps for installing single rod probes.

Installing the Transmitter

Procedures for attaching the transmitter unit.

Wiring

Electrical connection procedures.

General Purpose or Non-Incendive (CI I, Div. 2)

Wiring instructions for general purpose installations.

Intrinsically Safe

Wiring requirements for intrinsically safe installations.

Explosion Proof

Wiring procedures for explosion-proof environments.

Configuring the Transmitter

Setup and calibration procedures.

Transmitter Display and Keypad

Details on using the transmitter's interface and controls.

Model 705 Menu: Step-By-Step Procedure

Detailed configuration steps for the Model 705 menu.

Measurement Type: Level Only (Loop Control = Level)

Configuration steps for level-only measurement.

Measurement Type: Level and Volume (Loop Control = Volume)

Configuration for level and volume measurement.

Measurement Type: Interface Level (Loop Control = Interface Level)

Configuration for interface level measurement.

Offset Description

Explanation of the Level Offset parameter.

Strapping Table Description

Procedure for linearizing output for odd-shaped vessels.

Configuration Using HART

Setup and communication via HART.

Connections

How to connect a HART communicator.

Display Menu

Overview of the HART communicator's display menu.

FOUNDATION fieldbus Digital Communications

Details on integrating with Fieldbus systems.

Description

Overview of FOUNDATION fieldbus system.

Device Configuration

Configuration steps for Fieldbus devices.

Reference Information

Description

General overview of the ECLIPSE Level Transmitter.

Theory of Operation

Explanation of the technology and principles.

Micropower Impulse Radar

Explanation of the MIR technology.

Interface Detection

How the device detects interface levels.

Troubleshooting

Diagnosing and resolving common problems.

Troubleshooting System Problems

Common system issues and their solutions.

Status Messages

Interpreting diagnostic messages and status indicators.

Agency Approvals

Certifications and compliance standards.

Parts

Information on replacement and spare parts.

Replacement Parts

List of components available for replacement.

Specifications

Technical details and performance data.

Functional

Functional characteristics and parameters.

Performance - Model 705

Performance metrics and accuracy details.

Physical

Physical dimensions and mounting information.

Model Numbers

Product identification codes.

Transmitter

Breakdown of transmitter model number codes.

Probe

Breakdown of probe model number codes.

Glossary

Assured Quality & Service

Service Policy

Details on warranty, repairs, and service.

Return Material Procedure

Steps for returning materials for service or repair.

Magnetrol eclipse 705 Specifications

General IconGeneral
BrandMagnetrol
Modeleclipse 705
CategoryMeasuring Instruments
LanguageEnglish