Guided Wave Radar
Level Transmitter
Enhanced Model 705
Software v3.x
Installation and Operating Manual
2014/68/EU

Table of Contents

Other manuals for Magnetrol eclipse 705

Questions and Answers

  • S
    Susan SanchezAug 23, 2025
    How to stabilize fluctuating LEVEL and % OUTPUT values on Magnetrol eclipse 705?
    • D
      dboydAug 25, 2025
      If the LEVEL and % OUTPUT values are fluctuating, it could be due to turbulence. To stabilize the readings, increase the Damping factor.
  • G
    Gary DavisSep 1, 2025
    How to troubleshoot 'EOP High' error on Magnetrol Measuring Instruments?
    • E
      Emily WoodSep 1, 2025
      If the End of Probe signal is out of range, ensure the Probe Length is entered correctly.
  • N
    nmasonSep 1, 2025
    How to resolve 'Lvl
    • P
      poolerachelSep 2, 2025
      If the apparent position of the upper level pulse is beyond the end of the probe, check the entered Probe Length and change the Threshold to Fixed.
  • A
    Ashlee BowenSep 2, 2025
    How to troubleshoot 'No Fiducial' error on Magnetrol eclipse 705 Measuring Instruments?
    • J
      Jonathan RossSep 2, 2025
      If the fiducial signal is not being detected, check the connection between the probe and the transmitter. Also, check for moisture on top of the probe and for a damaged gold pin in the high-frequency connector.
  • S
    Sharon McmillanSep 3, 2025
    What does 'May be Flooded' mean on Magnetrol eclipse 705 and how to resolve it?
    • D
      Dr. Joann YoungSep 3, 2025
      If there is a loss of level signal possibly due to flooding (Twin Rod probes only), decrease the level in the vessel. You can also set the Dielectric to a lower range value or replace it with a Model 7xR Overfill probe.
  • B
    Blake LopezSep 4, 2025
    What does 'High Volume Flt' mean on Magnetrol Measuring Instruments and how can it be fixed?
    • M
      Melissa WhiteSep 4, 2025
      If the level is more than 5% above the highest point in the strapping table, verify the strapping table is entered correctly. The signal amplitude may also be lower than desired.
  • G
    George MosleySep 4, 2025
    How to resolve 'Hi Temperature' warning on Magnetrol eclipse 705 Measuring Instruments?
    • P
      Patricia MeyersSep 4, 2025
      If the present temperature in the electronics compartment is above 80°C, the transmitter may need to be moved to ensure the ambient temperature is within specification, or change to a remote mount transmitter.
  • J
    judy91Sep 5, 2025
    How to resolve 'Lo Temperature' warning on Magnetrol eclipse 705 Measuring Instruments?
    • R
      Rebecca CoxSep 5, 2025
      If the present temperature in the electronics compartment is below -40°F (-40°C), the transmitter may need to be moved to ensure the ambient temperature is within specification, or change to a remote transmitter.
  • L
    Lisa AndersonSep 6, 2025
    How to fix inaccurate LEVEL, % OUTPUT, and LOOP values on Magnetrol Transmitter?
    • A
      Andrew AlvaradoSep 6, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all inaccurate, the basic configuration data might be questionable. Try reconfiguring the Probe Model, Probe Mount, Probe Length, or Level Offset. Also, ensure the Level is accurate and verify the 4 mA and 20 mA Loop values.
  • P
    Patrick RitterSep 7, 2025
    What to do if LEVEL, % OUTPUT, and LOOP values fluctuate on Magnetrol Transmitter?
    • M
      Mario CarrSep 7, 2025
      If the LEVEL, % OUTPUT, and LOOP values are fluctuating, it might be due to turbulence. Increase the Damping factor until the readings stabilize.

Summary

QuickStart Installation

Getting Started

Prerequisites and initial steps for installation.

QuickStart Mounting

Procedures for mounting the transmitter and probe.

QuickStart Wiring

Steps for making electrical connections.

QuickStart Configuration

Basic setup and configuration of the transmitter.

Complete Installation

Unpacking

Procedures for safely unpacking the instrument.

Electrostatic Discharge (ESD) Handling Procedure

Safety guidelines for handling sensitive electronic components.

Before You Begin

Preparatory checks and considerations before installation.

Mounting

Details on probe and transmitter mounting procedures.

Installing a Coaxial Probe

Specific steps for installing coaxial probes.

Installing a Twin Rod Probe

Specific steps for installing twin rod probes.

Installing a Single Rod Probe

Specific steps for installing single rod probes.

Installing the Transmitter

Procedures for attaching the transmitter unit.

Wiring

Electrical connection procedures.

General Purpose or Non-Incendive (CI I, Div. 2)

Wiring instructions for general purpose installations.

Intrinsically Safe

Wiring requirements for intrinsically safe installations.

Explosion Proof

Wiring procedures for explosion-proof environments.

Configuring the Transmitter

Setup and calibration procedures.

Transmitter Display and Keypad

Details on using the transmitter's interface and controls.

Model 705 Menu: Step-By-Step Procedure

Detailed configuration steps for the Model 705 menu.

Measurement Type: Level Only (Loop Control = Level)

Configuration steps for level-only measurement.

Measurement Type: Level and Volume (Loop Control = Volume)

Configuration for level and volume measurement.

Measurement Type: Interface Level (Loop Control = Interface Level)

Configuration for interface level measurement.

Offset Description

Explanation of the Level Offset parameter.

Strapping Table Description

Procedure for linearizing output for odd-shaped vessels.

Configuration Using HART

Setup and communication via HART.

Connections

How to connect a HART communicator.

Display Menu

Overview of the HART communicator's display menu.

FOUNDATION fieldbus Digital Communications

Details on integrating with Fieldbus systems.

Description

Overview of FOUNDATION fieldbus system.

Device Configuration

Configuration steps for Fieldbus devices.

Reference Information

Description

General overview of the ECLIPSE Level Transmitter.

Theory of Operation

Explanation of the technology and principles.

Micropower Impulse Radar

Explanation of the MIR technology.

Interface Detection

How the device detects interface levels.

Troubleshooting

Diagnosing and resolving common problems.

Troubleshooting System Problems

Common system issues and their solutions.

Status Messages

Interpreting diagnostic messages and status indicators.

Agency Approvals

Certifications and compliance standards.

Parts

Information on replacement and spare parts.

Replacement Parts

List of components available for replacement.

Specifications

Technical details and performance data.

Functional

Functional characteristics and parameters.

Performance - Model 705

Performance metrics and accuracy details.

Physical

Physical dimensions and mounting information.

Model Numbers

Product identification codes.

Transmitter

Breakdown of transmitter model number codes.

Probe

Breakdown of probe model number codes.

Glossary

Assured Quality & Service

Service Policy

Details on warranty, repairs, and service.

Return Material Procedure

Steps for returning materials for service or repair.

Magnetrol eclipse 705 Specifications

General IconGeneral
BrandMagnetrol
Modeleclipse 705
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals