SIL Certified Safety Manual
for E3 Modulevel
®
Model E3X-XXXX-SXX
Liquid Level
Displacer Transmitter
This manual complements and is intended to be used with the
Magnetrol
®
E3 Mod ulevel
®
Liquid Level Displacer Transmitter
Installation and Operating manual (Bulletin 48-635).
Safety Function
The HART
®
version of the E3 Modulevel
®
transmitter will
measure level and transmit a signal proportional to that level
within the stated safety accuracy of ±2% of span (or the
measured error published in I/O Manual 48-635, whichever
is greater). In addition, when continuous, automatic diagnos-
tics detect that the transmitter cannot perform this function,
the output will be driven to the customer-specified out-of-
range signal (i.e., 3.6 mA or 21 mA).
The E3 MODULEVEL is certified for use in low demand
level measurement applications.
Application
The HART
®
version of the E3 MODULEVEL level trans-
mitter can be applied in most process or storage vessels, bri-
dles, and bypass chambers up to the transmitter’s rated tem-
perature and pressure. The E3 MODULEVEL can be used
in liquids, clean or dirty, light hydrocarbons to heavy acids
(SG=0.23 to 2.20) to meet the safety system requirements of
IEC 61508 (Edition 2.0, 2010).
Benefits
• Level protection to SIL 3 as certified by exida Certification
per IEC 61508.
• Level ranges from 14 to 120+ inches
(356 to 3048+ mm).
• Process temperatures to +850 °F (+454 °C) for non-steam
applications, +800 °F (+427 °C) for steam applications
• Process pressures to 5150 psi (355 bar).
• Continuous self-test with 22 mA or 3.6 mA fault indica-
tion fully compliant with NAMUR NE 43.
• IS, XP, and Non-Incendive approvals.
• Emission and immunity compliance to EN 61326.
• Two-wire, loop-powered transmitter for level,
interface, or density measurement.