13
Confirm the ECO selecting interface. After selecting ON or OFF, press and hold
the function setting key for more than half a second (less than 2 seconds). Now, the
ECO setting function is completed and the “ON” or “OFF” below the “ECO” will light
without flash.
Set the ECO tolerance range. Short press the scroll key or for more than half a
second (shorter than 2 seconds)to select the voltage range in percentage.
+5%,+10%,+15%,+25%(default is +25%)then short press function setting key
for more than half a second (shorter than 2 seconds)to confirm the selection, then to
set the minus range
To set the minus range in the same way.
Exit from the setting interface. Press and hold function setting key for more
than 2 seconds, exit from the setting interface and turn to main interface.
4.3.2 Bypass mode setting(2)
Enter the setting interface. Press and hold the function setting key for more than
2 seconds, then come to setting interface, Press and hold the function setting
key for more than half a second(less than 2 seconds), select the function setting,
choose the bypass output interface, at the moment, the letters “bPS” will flash
Enter the Bypass output selecting interface. Press and hold the function setting
key for more than half a second(less than 2 seconds), then come to setting
interface of bPS, at this time, the letters “bPS” will light for a long time. The “ON”