9. TABLE OF SEETINGS.
DESCRIPTION OF THE
PARAMETER
SYMBOL
SETTING RANGE
accessing the settings
UC0
access code
regulator operation mode
C9
0 cooling
1 heating
limitation of the lower
value for the control
temperature range
b1
setting the temperature from -40
O
C to
+120
O
C, every 1.0
O
C
limitation of the upper
value for the control
temperature range
b2
setting the temperature from -40
O
C to
+120
O
C, every 1.0
O
C
control hysteresis
HI
setting the temperature:
from 0.2
O
C to 10
O
C, every 0.2
O
C for the
range from -10
O
C to +100
O
C
from 1.0
O
C to 10
O
C, every 1.0
O
C for the
range of <-10
O
C and > + 100
O
C
minimum operation time
of the chiller (unit)
CA
0.00 inactive
>0.00 active: setting the time from 1 min. to
60 min., every 1 min.
maximum operation time
of the chiller (unit)
CC
0.00 inactive
>0.00 active: setting the time from 0,5 h to
9,5 h, every 0,5 h
minimum standstill time
of the chiller (unit)
CF
0.00 inactive
>0.00 active: setting the time from 1 min. to
60 min., every 1 min.
time after which the chiller
(unit) is turned off after
the flap of the milk tank
is opened
AF
0.00 inactive
>0.00 active: setting the time from 0,1 min.
(6 sec.) to 15 min., every 0,1 min. (6 sec.)
stirrer operation mode
F0
0 operation according to the times set in E1
and E2, regardless of the operation of the
chiller (unit)
1 continuous operation while the chiller
(unit) is running; when the chiller is on
standby, the stirrer operates according to the
times set in E1 and E2
2 as in setting 1, but disabling with the
stirrer's operation button causes its operation
only during the operation of the chiller
3 as in setting 1, but the button that disables
the stirrer operation is inactive
4 continuous operation, regardless of the
operation of the chiller (unit) and times set in
E1 and E2
standstill time of the stirrer
E1
setting the time from 1 min. to 60 min., every
1 min.
operation time of the
stirrer
E2
setting the time from 1 min. to 60 min., every
1 min.