EasyManua.ls Logo

M&C LA Series - Electronic Controller LA1.1 Connections

M&C LA Series
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.mc-techgroup.com LA | 1.01.01 17
13.1.1 ELECTRONIC CONTROLLER LA1.1
The following steps must be carried out for electrical connection (see Figure 4):
• Loosen the 4 lid screws and remove the lid.
• Lead the connection cables through the respective clamp fitting.
• The electrical connection of the sensor LA1S or LA25S is made according the colors on the
terminals 5 = brown and 6 = white.
Old sensors of type LA1, LA25 and LA1-H are to be connected to terminals 5 = brown and 8 =
white. In this case, a bridge must be installed between terminals 6 and 7.
NOTE!
If the older sensor LA1, LA25 or LA1-H is connected the same way as the
new sensor LA1S, the function of the electronic is inverted: no liquid = alarm,
liquid = OK.
NOTE!
If a new sensor LA1S is connected the same way as the old sensor LA1, LA25
or LA1-H no line break control is existing.
• The voltage supply is connected to terminals 1 = L, 2 = N and 3 = PE.
• The alarms are connected to terminals 12, 22 = alarm.
• The center contact is connected to terminals 11, 21.
• The relay contact 14, 24 = OK is energized in the good state.