EasyManuals Logo

Manitowoc I0320 User Manual

Manitowoc I0320
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
Part Number STH038 5/12 143
WATER TROUGH OVERFILLING DURING THE
FREEZE CYCLE
Step 1 Press the power button and turn off the ice
machine.
Step 2 If water continues to flow with the ice machine
off, disconnect power. If water continues to flow verify
water pressure is below 80 psig before replacing the
water inlet valve.
Step 3 Check water level probe mounting and verify
secure wiring connections at the probe and control
board.
Step 4 Scroll to Service/Diagnostics/Inputs and press
down arrow until Wtr Low and Wtr High are displayed.
No is displayed - Control board is not receiving a
sensing water signal. Continue with step 5.
Yes is displayed - Control board is receiving a
sensing water signal. Clean the water level probe
and test run.
Step 5 Start a new freeze cycle by pressing the
power button.
Step 6 Wait until the pre-chill cycle begins, then
jumper water level probe connection #2 & #3 at the
control board.
A. Water level light energizes and water flow
stops - Repair wire or replace water level
probe.
B. Water level light does not energize and water
continues to flow - Replace control board.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc I0320 and is the answer not in the manual?

Manitowoc I0320 Specifications

General IconGeneral
BrandManitowoc
ModelI0320
CategoryIce Maker
LanguageEnglish

Related product manuals