Part Number 000014141 Rev 11 12/23 27
Section 2 Installation
MAXIMUM LINE SET DISTANCE
FORMULA
Step 1.
Measured Rise (R) 35 feet (10.7 meters)
Maximum _____ x 1.7 =
_____ Calculated Rise
Step 2.
Measured Drop (D) 15 feet (4.5 meters)
Maximum _____ x 6.6 =
_____ Calculated Drop
Step 3.
Measured Horizontal Distance (H) 100 feet
(30 meters) Maximum
_____ Horizontal Distance
Step 4.
Total Calculated Distance 150 feet (45
meters) Maximum
_____ Total Calculated
Distance
Notice
The refrigeration system warranty will
not apply if the Manitowoc Ice Machine
and Manitowoc CVD Condensing Unit are
not installed according to specifications.
This warranty also will not apply if the
refrigeration system is modified with a
condenser, heat reclaim device, or other
parts or assemblies not approved by
Manitowoc.
REMOTE CONDENSER MODELS
Additional Refrigerant
Ice
Machine
Remote
Condenser
Additional
Refrigerant Added
to Nameplate
Charge for 50'
to 100' (15 to 30
Meter) Line Sets
IF0500N JCF0500 1.5 lbs - 680 g
IT0500N JCT0500 1.5 lbs - 680 g
IF0600N JCF0900 1.5 lbs - 680 g
IT0750N JCT1200 2.0 lbs - 907 g
IT0900N JCT1200 2.0 lbs - 907 g
IF0900N JCF0900 2.0 lbs - 907 g
IT1200N JCT1200 2.0 lbs - 907 g
IT1500N JCT1500 2.0 lbs - 907 g
IT1900N JCT1500 2.0 lbs - 907 g
Line Set / Model
Line Set
Discharge
Line
Liquid
Line
Model
RF
20/35/50
R404A
1/2 inch
(13 mm)
5/16 inch
(7.9 mm)
IF0500N
IF0600N
IF0900N
RT
20/35/50
R410A
1/2 inch
(13 mm)
5/16 inch
(7.9 mm)
IT0500N
IT0750N
IT0900N
IT1200N
RL
20/35/50
R410A
1/2 inch
(13 mm)
3/8 inch
(9.5 mm)
IT1500N
IT1900N
NOTE: R404A lines = white protective caps.
R410A lines = pink protective caps.
All line sets must be insulated with 1/4" Armaflex.