66 Part Number STH039 8/13
4. Compare the actual freeze cycle suction temperature
(Step 3) to the published freeze cycle time and temperature
comparison (Step 2B). Determine if the suction
temperature is high, low or acceptable.
Example:
In this example, the suction temperature is considered
high throughout the freeze cycle. It should have been:
Approximately -6 (at 1 minute) – not -1
Approximately -12 (at 10 minutes) – not -6
Approximately -17 (at 20 minutes) – not -12
Step