–83–
Refrigeration System
Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control (remotes)
Defective harvest valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensable in refrigeration system
Plugged or restricted high side refrigerant lines or
component
Safety Limit #2
Refer to page 75 for control board identification and
safety limit operation.
Control Board with Black Microprocessor
- Harvest
time exceeds 3.5 minutes for 3 consecutive harvest
cycles.
or
Control Board with Orange Label on
Microprocessor - Harvest time exceeds 3.5 minutes
for 500 consecutive harvest cycles.
Possible Cause Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
Water System
Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely
mounted to the evaporator
Low water pressure (20 psig min.)
Loss of water from sump area
Clogged water distribution tube
Dirty/defective water fill valve
Defective water pump