DISCHARGE PRESSURE HIGH CHECKLIST
Problem
Cause
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
Restricted Condenser Air Flow
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air recirculation
Dirty condenser filter
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Restricted Condenser water flow
Low water pressure (20 psi min.)
High inlet water temperature (90°F/32.2°C max.)
Dirty condenser
Dirty/Defective water regulating valve
Water regulating valve out of adjustment
Improper Refrigerant Charge
Overcharged
Non-condensable in system
Wrong type of refrigerant
Other
Non-Manitowoc components in system
High side refrigerant lines/component restricted
(before mid-condenser)
Defective head pressure control valve