34
WATER PUMP WON’T RUN
1. Water pump winding closed?
Yes-rebulid or replace water pump.
No-Water Pump Relay LED on control board lit?
Yes:repair wiring
No: rebulid or replace control board
HOT GAS VALVE WON’T ENERGIZE
1. Line voltage at hot gas valve?
Yes - Replace hot gas valve coil.
No - Hot gas valve Relay LED on control board lit?
Yes:repair wiring
No:rebulid or replace control board
WATER INLET VALVE WON’T ENERGIZE
1. Line voltage at water inlet valve?
Yes - Replace water inlet valve coil.
No - water inlet valve Relay LED on control board
lit?
Yes:repair wiring
No:rebulid or replace control board