57
Check Procedure
Make sure bulb is inserted correctly 35.5 cm in the
bulb well. Disconnect the wires from the bin thermostat
and check the resistance across the terminals.
NOTE:
After covering/uncovering the bulb holder with
ice, wait at least three minutes to allow the thermostat
to react. (Open/Close)
!
Warning
Disconnect electrical power to the entire ice
machine before proceeding.
No Ice on Bulb Ice on Bulb Result
Closed (O) Open (OL) Thermostat good
Open (OL) Closed (O)
Replace
thermostat