9.3.11 Low pressure protection diagnosis and solution (P6)
Error Code
Malfunction conditions When the pressure of system reach a certain value, the low
pressure protector will switch off. After the pressure returns to
normal, the protection code will disappear.
Possible causes ● Wiring error
● Pressure protector faulty
● Fan motor faulty
● PCB faulty
● System problems.
Troubleshooting:
between the low pressure
protector and main control
board is connected well or
correctly
between the low pressure
protector and main control
board is connected well or
correctly
Method: Disconnect the
plug. Measure the
resistance of the low
pressure protector. If the
protector is normal the value
is o
Method: Disconnect the
plug. Measure the
resistance of the low
pressure protector. If the
protector is normal the value
is o
Yes
Connect it well
Replace outdoor main board
Replace outdoor main board
Replace low pressure protector
Replace low pressure protector
pressure protector
is broken
pressure protector
is broken
Check whether the outdoor
ambient temperature is too
low
Check whether the outdoor
ambient temperature is too
low
Stop the unit
Yes
Open fully valve core of high
pressure valve
Open fully valve core of high
pressure valve
Check whether valve core of
high pressure valve is
opened
Check whether valve core of
high pressure valve is
opened
Check if the indoor fan runs
properly in cooling mode
Check if the indoor fan runs
properly in cooling mode
please refer to the solution of [fan
speed has been out of control
malfunction]. Find out the cause and
have it solved.
please refer to the solution of [fan
speed has been out of control
malfunction]. Find out the cause and
have it solved.
No
Yes
Yes
Check whether the
refrigerant system is ok
Check whether the
refrigerant system is ok
Refrigerant is not enough add the
Refrigerant is not enough add the
refrigerant
No