MINT – IO
REF NO: m25A/om/101
Issue No: 11
As shown in figure, data for slave parameters for read, store from starting
address 0 to 1025 with the base address of 40001 and data for slave
parameters for write, store from starting address 1 to 1025 with the base
address of 41026.
3.2.2 mINT CP configuration address
User can configure serial communication and Ethernet communication at
addresses shown in following table.
Address
Parameter
Min
value
Max
Value
Description
COM1
45001
Baud rate
1
5
1 = 9600(Default),
2 = 19200,
3 = 38400,
4 = 57600,
5 = 115200,
45002
Parity
0
2
0 = None(Default),
1 = Even,
2 = Odd
45003
Stop Bits
1
2
1 = 1 Stop bit(Default),
2 = 2 Stop bits
45004
Data Length
8
8
8 = 8 Data Bits
COM2
45005
Baud rate
1
5
1 = 9600(Default),
2 = 19200,
3 = 38400,
4 = 57600,
5 = 115200
45006
Parity
0
2
0 = None(Default),
1 = Even,
2 = Odd
45007
Stop Bits
1
2
1 = 1 Stop bit(Default),
2 = 2 Stop bits
45008
Data Length
8
8
8 = 8 Data Bits
45013
Enable-
COM-1
0
1
0 = Disable,
1= Enable(Default),
Slave
parameter
data for
read
2048
1025
1024
0
MEM.ADDR
Slave
parameter
data for
write
Modnet Addr. 40001
Modnet Addr. 41026