1.2 Indoor units specifics
MODELS BDLM26A2 BDLM36A2 BDLM53A2
Power supply
V-Ph, Hz
230V
220 ~ 240V ○,
1
, 50Hz
kW 2.600 3.500
5.300
Total capacity
Btu/h 8,8 11,9
18,0
Power input W 10 10
55
Cooling
Absorbed current A 0,04 0,04
0,3
kW 2.800 3.800
5.800
Total capacity
Btu/h 9,5 12,9
19,7
Power input W 10 10
55
Heating
Absorbed current A 0,04 0,04
0,3
Air flow volume
(SH/H/M/L)**
(m
3
/h)
500 630
850
Dehumidifying volume l/h 0,6
1,4
1,8
Fan motor speed (SH/M/L) (r/min) 1320/1200/1100/950 1280/1080/1000/920
1420/1250/1150/105
Fan Motor Capacitor μF 1 1
1,5
Fan motor full load Amp (FLA) A 0,144 0,22
0,31
Output of fan motor W 10 20
20
Motor model FN10A-PG FN20J-PG
FN20V-PG
Fan type-piece
Cross flow fan – 1
Diameter-Length mm Ø85 X 596 Ø92 X 645
Ø98 X 710
Evaporator
Aluminum fin-copper tube
Pipe diameter
mm Ø7
Row-Fin gap mm 2-1,5 2-1,4
2-1,4
Indoor Coil
Coil length (l)xheight (H)xcoil width (L)
mm 581X267X25,4 690X267X25,4
715×304,8x25,4
Swing motor model MP24AA
MP28VB
Output of swing motor W 1,5 1,5
2,0
Fuse
A PCB 3,15A
Indoor sound level (H/M/L) dB(A) 39/34/28 40/35/30
43/40/35
Dimension (W/D/H) mm 790X174X265 845X180X275
940/200/298
Dimension of package (W/D/H) mm 870x248X355 918x258X370
1013X288X395
Net weight/Gross weight
kg 9/11 10/12,5
13/16
Liquid pipe
mm Ø6 Ø6
Ø6
Gas pipe (to indoor unit)
mm Ø9,52 Ø9,52
Ø12,7
The data of specifications are subject to change without prior notice. Please refer to the actual data specified on the
nameplate of the unit.
Note: Test conditions:
Indoor side state Outdoor side state
Standard condition
Dry bulb temp. °C Wet bulb temp. °C Dry bulb temp. °C Wet bulb temp. °C
Rated cooling 27 19 35 24
Max. cooling 32 23 48 26
Min. cooling 21 15 18 -
Rated heating 20 15 7 6
Max heating 27 - 24 18
Min. heating 20 15 -15 -16
3) Microphone at a distance of 1m from the unit.
Approximate calculation from Sound Pressure Level to Sound Power Level:
- Average Sound Pressure Level
p
L =10*lg
21
*1.0*1.0
1010(*2/1
PP
LL
+
.
1P
L
: Sound pressure level of front test point.
2P
L
: Sound pressure level of side test point for indoor unit
21
,
PP
LL .
- Approximate Sound Power Lever
pW
LL =
+10.