Loading...
33
Termostato remoto da posizionare a muro -
Using a remote thermostat o be positioned on the wall
-
Verwenden Sie einen Fernthermostat -
À l’aide d’un thermostat à distance, placez-vous sur le mur
-
Utilice un termostato remoto para colocarlo en la pared
A.FRIZZIERO A.FRIZZIERO
1/2
MASTER
blue wire
brown wire
blue wire
brown wire
HEATING
VALVE
COOLING
VALVE
WALL PAD
always 4 pipe
setted
N
HI
MED
LOW
VAL1 VAL2
L
WALL PAD
LOW
VAL1VAL2
TO SLAVE UNIT
DELAY
MED
HI N
CONTACT
L
N
PUMP
L
N
FILTER
L
N
HEATER
N
COOLING
L
HEATING
FUSE
L
N
GND
IN AC230V
DC MOTOR
ROOM
COM1
STEP1
DIP SWITCH
3
2
1
ON
ME
54
WATER
N
L
KEEP ATTENTION TO DON'T
INVERT PHASE AND
NEUTRAL IN BOTH MASTER
AND SLAVE UNITS.
230V-50 Hz
N
L1
PE
HI
MED
LOW
VAL1
TO FIRST SLAVE
VAL2
n11
l11
COIL
TEMPERATURE
PROBE (2)
(OPTIONAL)
WINDOW
CONTACT (1)
(2) THE PROBE MUST BE POSITIONED IN THE COIL
ALUMINUM FINS, IN PROXIMITY OF THE INLET. IT
WILL MEASURE THE WATER TEMPERATURE AND IN
HEATING MODE, THE FAN WILL RUN ONLY IF THE
TEMPERATURE IS OVER THAN THE 35°C (MINIMUM
THERMOSTAT FUNCTION)
(1) IT IS POSSIBLE TO REMOVE THE ELECTRIC BRIDGE BY
FACTORY AND TO USE THE CONTACT AS A
OCCUPANCY SENSOR. IN THIS SENSE, IF THE CONTACT
IS CLOSED, THE UNIT WILL RUN IN ACCORDANCE TO
ITS SETTINGS. INSTEAD IF THE CONTACT IS OPENED,
THE UNIT WILL BE TURNED OFF AFTER 30 SECONDS.
WHEN THE CONTACT IS CLOSED AGAIN, THE UNIT
WILL RUN IN ACCORDANCE TO ITS SETTING.
SW1~3: Motor speed setting
DIP switch description
SW4
OFF
ON
Control setting
Wall Pad
Infrared Handset Remote Control
SW5
OFF
ON
Pipes Setting
2 pipes
4 pipes
Standard setting as indicated above.
Refer to the manual, for different RPM settings.
Ventilconvettore
Fan coil
Gebläsekonvektoren
Ventilconvecteureurs
Ventilconvectores
DIP SWITCH :
1 ON
2 ON
3 ON
4 OFF
5 refer to table below
REVERSO + 4 PIPE REMOTE CONTROL complete
HEATER
REV0003A
20/01/2020