EasyManua.ls Logo

MAXA GRIMPER FAN Series - Page 34

MAXA GRIMPER FAN Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
A.FRIZZIERO A.FRIZZIERO
PE
ME
KEEP ATTENTION TO DON'T
INVERT PHASE AND
NEUTRAL IN BOTH MASTER
AND SLAVE UNITS.
2/2
SLAVE
HI
MED
LOW
VAL1
TO NEXT SLAVE
TO MASTER OR
PREVIOUS SLAVE
VAL2
HI
MED
LOW
VAL1
VAL2
n11
l11
n11
l11
N HI
MED LOW
VAL1 VAL2
L
WALL PAD
LOW
VAL1VAL2
TO SLAVE UNIT
DELAY
MED
HI N
CONTACT
L
N
PUMP
L
N
FILTER
L
N
HEATER
N
COOLING
L
HEATING
FUSE
L
N
GND
IN AC230V
DC MOTOR
ROOM
COM1
STEP1
DIP SWITCH
3
2
1
ON
ME
54
WATER
N
L
REV0003A
20/01/2020
REVERSO + 4 PIPE REMOTE CONTROL complete
(2) THE PROBE MUST BE POSITIONED IN THE COIL
ALUMINUM FINS, IN PROXIMITY OF THE INLET. IT WILL
MEASURE THE WATER TEMPERATURE AND IN HEATING
MODE, THE FAN WILL RUN ONLY IF THE TEMPERATURE IS
OVER THAN THE 35°C (MINIMUM THERMOSTAT
FUNCTION)
(1) IT IS POSSIBLE TO REMOVE THE ELECTRIC BRIDGE BY
FACTORY AND TO USE THE CONTACT AS A
OCCUPANCY SENSOR. IN THIS SENSE, IF THE CONTACT
IS CLOSED, THE UNIT WILL RUN IN ACCORDANCE TO
ITS SETTINGS. INSTEAD IF THE CONTACT IS OPENED,
THE UNIT WILL BE TURNED OFF AFTER 30 SECONDS.
WHEN THE CONTACT IS CLOSED AGAIN, THE UNIT
WILL RUN IN ACCORDANCE TO ITS SETTING.
EACH SINGLE SLAVE UNIT RECEIVES IMMEDIATELY
SETTINGS FROM THE MASTER OR THE PREVIOUS SLAVE
CONNECTED TO THE SAME LINE, BUT IT WILL BE
TURNED ON WITH A DELAY OF 15 SECONDS AFTER THE
STARTING UP OF THE PREVIOUS UNIT.
SW1~3: Motor speed setting
DIP switch description
SW4
OFF
ON
Control setting
Wall Pad
Infrared Handset Remote Control
SW5
OFF
ON
Pipes Setting
2 pipes
4 pipes
Standard setting as indicated above.
Refer to the manual, for different RPM settings.
COIL
TEMPERATURE
PROBE (2)
(OPTIONAL)
WINDOW
CONTACT (1)
Ventilconvettore
Fan coil
Gebläsekonvektoren
Ventilconvecteureurs
Ventilconvectores
DIP SWITCH :
1 ON
2 ON
3 ON
4 OFF
5 refer to table below
blue wire
brown wire
blue wire
brown wire
COOLING
VALVE
HEATER

Related product manuals