EasyManua.ls Logo

MAXA i-32V514T - Refrigerant Handling and Leak Detection; Leak Detection Procedures; Refrigerant Removal and Charging

MAXA i-32V514T
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i-32V5 Air/water inverter heat pumps with axial fansi
35
Measure Completed Notes
11

On no account use possible sources of ignion for refrigerant detecon or
leak detecon.
Flame leak detectors or other detectors with open ames must not be used.
12

The following leak detecon processes are suitable for systems with ammable
refrigerants:
Leak detecon with electronic refrigerant detectors:
Electronic refrigerant detectors may not have the required sensi- vity or
may need to be calibrated to the relevant range. Carry out the calibraon in
refrigerant-free surroundings.
The refrigerant detector must be suitable for the R32 refriger- ant to be de-
tected.
The refrigerant detector must not contain any potenal sources of ignion.
Calibrate the refrigerant detector to the refrigerant used. Set the response
threshold to < 3 g/a, suitable for propane.
Leak detecon with liquid leak detectors:
Liquid leak detectors are suitable for use with most refrigerants.
! Please note
Liquid leak detectors containing chlorine may react with
the refrigerant. This could result in corrosion.
Do not use liquid leak detectors that contain chlorine.
Measures to take if a leak in the refrigerant circuit occurs:
Immediately exnguish all open ames in the vicinity of the heat pump.
If brazing/soldering work needs to be undertaken to remedy the leak, al-
ways extract all the refrigerant from the refrigerant circuit. Purge the site
to be brazed/soldered before and during the braz- ing/soldering work with
oxygen-free nitrogen.
13

When breaking into the refrigerant circuit to make repairs or for any other
purpose convenonal procedures shall be used. However, it is important that
best pracce is followed since ammability is a consideraon. The following pro-
cedure shall be adhered to:
- remove refrigerant;
- purge the circuit with inert gas;
- evacuate;
- purge again with inert gas;
- open the circuit by cung or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The
system shall be “ushed” with OFN to render the unit safe. This process may
need to be repeated several mes. Compressed air or oxygen shall not be used
for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
connuing to ll unl the working pressure is achieved, then venng to atmo-
sphere, and nally pulling down to a vacuum. This process shall be repeated unl
no refrigerant is within the system. When the nal OFN charge is used, the sys-
tem shall be vented down to atmospheric pressure to enable work to take place.
This operaon is absolutely vital if brazing operaons on the pipe-work are to
take place.
Ensure that the outlet for the vacuum pump is not close to any ignion sources
and there is venlaon available.
14

In addion to convenonal charging procedures, the following requirements
shall be followed.
Ensure that contaminaon of dierent refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeraon system is earthed prior to charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overll the refrigeraon system.
Before recharging, the system shall be pressure tested with OFN. The system
should be leak tested aer recharging but before commissioning. An addional
leak test must be performed before leaving the site.

Table of Contents

Other manuals for MAXA i-32V514T

Related product manuals