MAXA DC Fan Coil Unit
8
Model MI 26A1 35A1
Air flow
H/M/L
m
3
/h
425/410/320
680/550/504
H/M/L
CFM
250/241/188
400/324/297
Cooling
Capacity
H/M/L
kW
2.2/2.2/1.97
3.08/2.90/2.66
Water flow rate
H
L/h
378
530
Water pressure drop
H
kPa
23.1
42
Heating
Capacity
H/M/L
kW
3.02/2.85/2.35
4.34/3.77/3.35
Water pressure drop
H
kPa
22
40
Power supply
V/Ph/Hz
Power input
H
W
10.7
33
Sound pressure level
H/M/L
dB(A)
30/26/23
36/32/29
Fan motor
Type
Quantity
1
1
Fan
Type
Quantity
1
1
Coil
Row
Max. Working pressure
MPa
Coil length x height
mm
Fin spacing
mm
Fin type
Hydrophilic aluminium
Number of circuits
Diameter
mm
Body
Dimensions
W×H×D
mm
915×290×210
915×290×210
Packing
W×H×D
mm
1020×385×300
1020×385×300
Net weight
kg
12
12
Gross weight
kg
15.6
15.6
Pipe
connection
Water inlet/outlet pipe
inch
Drain pipe
mm
Note:
1. H: high speed; M: medium speed; L: low speed
2. Cooling Conditions: Entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°C WB.
Heating Conditions: Entering water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.
3. Noise is tested in semi-anechoic test room.