MAXA DC Fan Coil Unit
9
Model MI 42A1
Air flow
H/M/L
m
3
/h
850/692/586
H/M/L
CFM
500/407/345
Cooling
Capacity
H/M/L
kW
4.07/3.78/3.05
Water flow rate
H
L/h
700
Water pressure drop
H
kPa
34.9
Heating
Capacity
H/M/L
kW
5.69/4.14/3.63
Water pressure drop
H
kPa
29.7
Power supply
V/Ph/Hz
220-240/1/50
Power input
H
W
28
Sound pressure level
H/M/L
dB(A)
38/34/30
Fan motor
Type
DC Motor
Quantity
1
Fan
Type
Tangential fan
Quantity
1
Coil
Row
2
Max. Working pressure
MPa
1.6
Coil length x height
mm
785x26.74
Fin spacing
mm
1.5
Fin type
Hydrophilic aluminium
Number of circuits
7
Diameter
mm
Φ7
Body
Dimensions
W×H×D
mm
1070×315×210
Packing
W×H×D
mm
1180×410×300
Net weight
kg
14.7
Gross weight
kg
18.6
Pipe
connection
Water inlet/outlet pipe
inch
RC3/4
Drain pipe
mm
ODΦ20
Note:
1. H: high speed; M: medium speed; L: low speed
2. Cooling Conditions: Entering Water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°C WB.
Heating Conditions: Entering Water 50°C, entering air temperature 20°C, the same water flow as the cooling conditions.