12
1. Sensors that have been wired to indicated inputs MUST be “LEARNED” BEFORE they will be MONITORED.
2. Press and HOLD the STOP button & then the OPEN button together until beeping is heard, learn mode begins.
DO NOT press the OPEN button before the STOP button or learn mode will NOT begin (no beeping).
NOTE: Sensors wired to the PHOTO CLS NC input and OPEN ONLY NC input do NOT need to be “Learned”.
They are AUTOMATICALLY MONITORED”.
3. LEDs WILL turn ON for each detected “LEARNED” sensor that has been wired to the inputs.
If a sensor’s LED is NOT on, that sensor has a problem and it MUST be corrected before continuing.
Possible problems:
Photocells are out of alignment
Photocells are wired wrong - N.C. or N.O. depending on which photocells are used
Sensor is bad
When all LEDs are ON that should be ON, proceed to next step.
4. Press STOP button again within 5 min. to learn sensors and end learn mode, beeping stops.
Wired “Learned” Inputs will now be MONITORED.
NOTE: If STOP button is not pressed within 5 min., learn mode terminates.
If no “LEARNED” sensors are detected then factory default setting is restored (Inputs will NOT be Monitored).
MOTION CONTROL
OPEN STOP
CLOSE
MOTION CONTROL
OPEN
STOP
CLOSE
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN/CLS NC
GND
12VDC OUT
GND
CLS ONLY 10K
OPEN/CLS 10K
12VDC OUT
UL SENSOR N.C.UL SENSOR 10K
SENSOR
SENSO
SENSO
SENSO
SENSO
ENSO
ENS
ENS
NS
O
R 10K
O
R 10K
O
R 10K
O
R 10K
O
10K
10K
10
10
1
C
NSOR
R
R
R
R
R
1
1
1
C
SOR
R
R
R
R
R
R
1
SO
OR
R
R
R
R
R
R
R
SO
O
OR
R
R
R
R
R
R
SO
O
O
OR
R
R
R
R
R
SO
O
O
O
OR
R
R
R
SO
O
O
O
O
OR
R
O
O
O
O
O
O
O
O
O
O
O
L SEN
N
NS
S
S
S
S
S
SO
SO
O
O
L SEN
N
N
NS
S
S
S
S
S
S
L SEN
N
N
N
NS
S
S
S
S
S
L SEN
N
N
N
N
NS
S
S
S
L SE
EN
N
N
N
N
NS
S
S
SE
EN
N
N
N
N
N
N
SE
E
EN
N
N
N
N
SE
E
E
EN
N
N
SE
E
E
E
Indicated Inputs MUST be “LEARNED” before gate operator will MONITOR those sensors.
Unlearned Input
Unlearned Input
Unlearned Input
Unlearned Input
Factory Learned Input
Factory Learned Input
LEARN unlearned sensor inputs
Card Reader
Separate power
for Devices if required.
KeypadKey Switch
MAX OPEN Switch
(Overrides gate
disable switch)
Key will manually
release slide gate
Safety Open Device
Dry Contact
(N.O.)
(N.O.)
Telephone
Entry
Dry Contact (N.O.)
Normal Opening Devices
Dry Contact
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
CLOSINGOPENING
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
PROGRAM
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD
MAX
OFF
MAX
SENSE
MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
GATE SPEED
MAG
LOCK
UL
ENTRAP
PRIMARY/
SECONDARY
LINK
STOP CLOSE
MOTOR
INPUTS
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
INPUT
ERROR
BATTERY
BATTERY
IN USE
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN
OPEN
1 TIME
BATTERY VOLTAGE
E F1/2
RESET /
MANUAL
RELEASE
ID
PLUG
LINK
OK
MODULE
PORT
MOTOR
POSITION
INPUTS
SLIDER
LIMIT
SWING
LIMIT
GND
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN/CLS NC
GND
12VDC OUT
GND
GND
GND
GND
GND
GND
JOG RIGHT
JOG LEFT
TAMPER IN
TAMPER NO
GATE DISABLE
MANUAL RELEASE
KEYPAD / CARD
GND
(-)
(+)
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
CLS ONLY 10K
OPEN/CLS 10K
12VDC OUT
NO
COM
NC
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
GND
GND
LOOP PWR
OFF
PRIMARY
LEFT
ON/OFF
BATTERY
RIGHT
SECONDARY
ON
QUICK
CLOSE
OPEN
LEFT
OPEN
RIGHT
GATE
OFF
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
MATRIX III
OFF
OFF
3
1
14
16
MIN
16
MIN
12
9
7
3
1
14 12
9
7
UL SENSOR N.C.UL SENSOR 10K
POWER
MODE A MODE B
EXIT LOOP
LOOP
LOOP
CENTER
SAFETY
GATE OPEN
COM
GATE CLOSED
MIN
MATRIX III
SWING / SLIDE
Emergency OPEN
(Overrides gate
disable switch)
Emergency Open Device
(N.O.)
Stop
Com
External Alarm
Reset Button
Manual Release
Safety Device
PRESS
to RESET
MAGLOCK LED (Monitors Maglock):
ON - Locked OFF - Unlocked
Flashing - Problem with Maglock Power.
MAGLOCK DELAY:
You MUST select a time delay when using
a maglock. Maglock power disengages 1.5
sec or 2 sec before gate starts opening.
Dual Gate Operators using Maglock:
Primary gate opens FIRST. Install maglock
accordingly to account for this.
wiring opening device options
11
Gnd
NO
+
+
-
-
Maglock
Power
Power
Solenoid Lock
Bi-parting gates using locks:
Primary gate opens FIRST. Install
lock accordingly to account for this.
12 VDC
OR
24 VDC
Radio
Power
250 mA Max.
4-Wire
Radio
3-Wire
Radio
Radio Receivers
12V Power
Stand-Alone Keypad
less than 200 mA
(N.O.)
12
UL 325
2018 Standard - MAX 1500 PRO/2200 PRO/F18 PRO Matrix III Install Version 7d
+
-

Related product manuals