KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 19
+DISABLEMENTS: It is possible to temporarily disable loop(s), zone(s), device(s), and
sounder(s). This option would typically be necessary during maintenance of the system or
painting, construction workings, etc. on the site, where the fire alarm system is installed, to
avoid faulty alarms.
+Disable Loop: It is possible to disable desired loop(s).
+Disable Zone: It is possible to disable desired zone(s).
+Disable Device: It is possible to disable desired device(s).
+Disable Sounder: By selecting this option, it is possible to disable all sounders
connected to the sounder line outputs, all addressable sounders connected to the loop line
and all sounders connected to the sounder controller module.
+SET SYSTEM TIME: It is possible to make the adjustments of Year, Month, Day, Hour and
Minute. (The correct system time is vital in proper registration of events.)
+FIRE ALARM COUNTER: Total number of fire events, which occur after installation of the
fire alarm system, can be displayed.
+DELAY CONFIGURATION: It is possible to activate or deactivate all delay values which are
assigned to output devices through Loop Manager software.
+TEST: It is possible to test the system by activating loop(s), zone(s) and device(s) for a while
(Access level 3 Test Reset Delay). This allows the system to be tested by only one single
person.
+Loop Test: It is possible to test desired loop(s).
+Zone Test: It is possible to test desired zone(s).
+Device Test: It is possible to test desired device(s).
+ACCESS LEVEL 3:
c) Access level 3:
Special settings can be made from this menu. ‘Access Level 3’ option must be selected to get
access to ‘Access Level 3 Menu. “1,3,4,2” Password must be entered to Password Entry
field by using direction buttons. (This password can be personalized through Loop Manager
(Panel Settings - > Level 3 Password).)
ACCESS LEVEL 3 MENU
+Password Entry (Use direction buttons)
+Panel Configuration
+Event Logs
-Print Configuration
+Edit Event
+SLCU App. Software
+Contamination Control
-Analog Update
ACCESS LEVEL 3 MENU INSTRUCTIONS
+Password Entry (Use direction buttons):
+Panel Configuration: By selecting this option, special settings can be made
for the panel. The followings are available settings to be made.
-Panel General Settings:
-Supplier Name: The company name (and contact information)
information which will be displayed on panel screen in normal operating mode can be

Related product manuals