45
VENTING INFORMATION
Table 17. Vent Termination Clearances
Clearance Location
CANADIAN INSTALLATIONS
a
US INSTALLATIONS
b
Direct Vent (2-pipe) &
Conventional Vent (1-pipe)
Furnaces
Direct Vent
(2-pipe) Furnaces
Conventional Vent
(1-pipe) Furnaces
A
Clearance above grade, veranda, porch, deck,
balcony, or maximum expected snow level.
12 inches (30cm) 12 inches (30cm) 12 inches (30cm)
B
Clearance to window or door that may be opened.
6 inches (15cm) for appliances
< 10,000 Btuh (3kW)
6 inches (15cm) for appliances
< 10,000 Btuh (3kW)
4 ft. (1.2m) below or to side of opening;
1 ft. (300mm) above opening
12 inches (30cm) for appliances
10,000 Btuh - 100,000 Btuh (30kW)
9 inches (23cm) for appliances
10,000 Btuh - 50,000 Btuh (30kW)
36 inches (91cm) for appliances
> 100,000 Btuh (30Kw)
12 inches (30cm) for appliances
> 50,000 Btuh (30Kw)
C
Clearance to permanently closed window
***
D
Vertical clearance to ventilated soffi t located above the
terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal.
***
E
Clearance to unventilated soffi t.
***
F
Clearance to outside corner.
***
G
Clearance to inside corner.
***
H
Clearance to each side of center line extended above
meter/regulator assembly.
3 feet (91cm) within a height 15 feet
above the meter/regulator assembly
**
I
Clearance to service regulator vent outlet. 3 feet (1.83m)
**
J
Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance.
6 inches (15cm) for appliances
< 10,000 Btuh (3kW)
6 inches (15cm) for appliances
< 10,000 Btuh (3kW)
4 ft. (1.2m) below or to side of opening;
1 ft. (300mm) above opening
12 inches (30cm) for appliances
10,000 Btuh - 100,000 Btuh (30kW)
9 inches (23cm) for appliances
10,000 Btuh - 50,000 Btuh (30kW)
36 inches (91cm) for appliances
> 100,000 Btuh (30Kw)
12 inches (30cm) for appliances
> 50,000 Btuh (30Kw)
K
Clearance to mechanical air supply inlet. 6 feet (1.83m)
3 feet (91cm) above if within
10 feet (3m) horizontally
3 ft. (91cm) above if within
10 feet (3m) horizontally
L
Clearance above paved sidewalk or driveway located
on public property.
7 feet (2.13m)
c
*
7 ft. (2.13m)
M
Clearance under veranda, porch, deck, or balcony.
12 inches (30cm)
d
**
NOTES:
a
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Guide Code
b
In accordance with the current ANSI Z223.1 / NFPA 54 Natural Fuel Gas Code
c
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
d
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
*
For clearances not specifi ed in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included: “Clearance in accordance with local installation codes, and the requirements of the
gas supplier and the manufacturers installation instructions.” / “Dégagement conforme aux codes d’installation locaux, aux exigences du fournisseur de gaz et aux
instructions d’installation du fabricant”.
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED