EasyManuals Logo

McQuay AGR 080AS Product Manual

McQuay AGR 080AS
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Product Manual AGR-3 AGR 070A through 100A
39
electrical conduit to isolate sound through electrical conduit. Spring isolators are effective in reducing
the low amplitude sound generated by reciprocating compressors and for unit isolation in sound
sensitive areas.
Typical Chilled Water Piping
Flush the system water piping thoroughly before making connections to the unit evaporator. Install a
strainer of 40 mesh in the return water line before the inlet to the chiller. Design the water piping so the
chilled water circulating pump discharges into the evaporator inlet.
Connect the return water line to the evaporator inlet connection. Connect the supply water line to the
evaporator outlet connection.
Install and calibrate a flow switch in the horizontal piping of the supply (evaporator outlet) water line.
Provide drain connections at low points in the system to permit complete drainage of the system. Locate
air vents at the high points in the system to purge air out of the system. A vent connection on top of the
evaporator vessel allows air to be purged out of the evaporator. Purge air from the water system before
unit start-up to ensure adequate flow through the evaporator.
Install pressure gauges in the inlet and outlet water lines to the evaporator. Measure pressure drop
through the evaporator and compare to flow as shown in Figure 9. Vibration eliminators are
recommended in both the supply and return water lines.
Insulate chilled water piping to reduce heat loss and prevent condensation. Chillers not running in the
winter should have their water systems thoroughly drained to protect against freezing. If the chiller
operates year round, or if the system is not drained for the winter, protect the chilled water piping
exposed to outdoor temperature against freezing. Wrap the lines with a heater cable and add proper
amount of glycol to the system to further protect the system.
The total water volume in the system should be sufficient to prevent “on-off” cycling. Turnover rate
should not be less than 8 minutes for normal variable loads. Turnover rate for process cooling or a
constant load, should not be less than 6 minutes.
Chilled Water Piping
The thermostat sensor is factory mounted in the leaving water thermowell on AS units. If an optional
high return water sensor is provided, install sensor bulb in a field supplied tee or strap to the outside of
the water line.
Figure 18, Typical Chilled Water Piping

Other manuals for McQuay AGR 080AS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay AGR 080AS and is the answer not in the manual?

McQuay AGR 080AS Specifications

General IconGeneral
BrandMcQuay
ModelAGR 080AS
CategoryChiller
LanguageEnglish

Related product manuals