19
MCW-H
MODEL
WATER
FLOW

W.P.D

ENTERING AIR: DB21ºC
ENTERING WATER TEMPERATUREºC
40 45 50 55 60 65 70 75 80
W W W W W W W W W

0.12 3.2
430 540 690 830 950 1180 1370 1820 1980
0.18 7.3 530 680 780 940 1160 1360 1800 1980 2180
0.24 12.0 620
760 920 1170 1350 1780 1930 2160 2460
0.36 21.9 800 910 1150 1250 1730 1900 2150 2440 2640

0.12
3.7 790 980 1180 1380 1580 1780 1970 2170 2360
0.18 8.2 1000 1240 1490 1740 1990 2240 2490 2740 2980
0.24
13.5 1140 1420 1700 1990 2280 2560 2850 3130 3420
0.36 25.0 1340 1660 1990 2340 2660 3000 3330 3660 3990

0.12 5.2
1170 1430 1760 2040 2340 2620 2910 3190 3490
0.18 10.0 1430 1790 2860 2500 2860 3210 3580 3930 4280
0.24
14.8 1610 2010 2410 2790 3210 3600 4030 4420 4820
0.36 29.0 1900 2370 2830 3320 3790 4270 4740 5210 5630

0.12 8.2
1570 1980 2380 2760 3140 3570 3990 4370 4770
0.18 14.0 1890 2390 2890 3350 3790 4220 4800 5240 5730
0.24 20.7 2120 2700 3240
3790 4290 4870 5450 5990 6530
0.36 36.0 2520 3200 3850 4540 5180 5860 6530 7120 7830

0.12 2.4
1890 2350 2830 3290 3770 4240 4720 5180 5650
0.18 4.8 2270 2840 3400 3970 4540 5100 5660 6240 6800
0.24
7.8 2570 3200 3840 4480 5120 5760 6400 7050 7690
0.36 11.5 3040 3810 4560 5320 6080 6840 7600 8360 9130

0.3 5.5 2070 2600 3290 3800 4360 4790 6070 6440 7430
0.4 8.8 2830 3300 4240 4400 5660 6350 7090 7610 9290
0.5 12.8 3610 4090 5180 5400 6940 7550 9230 9620 10550
0.6 18.5 4060 4900 5290 6340 8510 9370 10150 11300 12380

0.3 6.0 2980 3540 4210 5230 5970 6440 7650 8270 9250
0.4 9.9 3650 4270 5650 6350 7150 7980 9414 10280 11080
0.5 14.6 4300 5200 6490 7580 8490 9400 10900 11900 12980
0.6 20.0 4830 5910 7660 8790 10420 11200 12380 13610 14850
NOTES:
1) THE HEATING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN
SPEED MUST MULTIPLY A CORRECTION FACTOR.
2) W.P.D:WATER PRESSURE DROP
Heating Capacity Correction Factors:
MODEL       
MEDIUM 0.8 0.78 0.78 0.81 0.83 0.8 0.81
LOW 0.58 0.56 0.57 0.58 0.62 0.6 0.61