11
MODEL
WATER
FLOW
W.P.D
ENTERING WATER TEMPERATUREºC
6 7 8 9 10
TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE
W W W W W W W W W W
0.24
5.6 1750 1280 1640 1260 1550 1230 1430 1180 1260 1130
0.33 9.7 1970 1440 1870 1400 1750 1400 1620 1370 1490 1330
0.42
14.8 2130 1570 1990 1530 1870 1490 1750 1480 1610 1450
0.51 21.6 2250 1650 2220 1620 1970 1580 1830 1530 1690 1510
0.36 4 2620 1940 2460 1890 2260 1850 2070 1820 2030 1790
0.48 9.2 2910 2140 2720 2100 2540 2070 2340 2040 2270 2000
0.6 13.2 3130 2300 2920 2240 2720 2210 2500 2170 2410 2150
0.72
18.7 3290 2430 3080 2370 2850 2340 2630 2300 2540 2240
0.42
7.3 3290 2390 3070 2340 2880 2300 2660 2260 2310 2210
0.6 13.8 3770 2670 3550 2740 3320 2710 3070 2690 2820 2640
0.78 21.6 4120 3020 3950 2990 3580 2950 3340 2920 3070 2880
0.96 31 4370 3160 4080 3140 3810 3110 3510 3070 3230 3040
0.72
18.7 5270 3830 4930 3800 4590 3760 4200 3700 3840 3570
0.9 32.7 5680 3970 5300 3920 4910 3830 4560 3780 4190 3700
1.08 38.2 6000 4190 5540 4010 5200 3960 4800 3920 4410 3920
1.26
50 6270 4350 5840 4300 5430 4230 5000 4210 4580 4140
1.14 12.5 7000 5150 6570 5070 6070 5010 5450 4910 4980 4790
1.44 18.7 7570 5290 7110 5220 6630 5180 6140 5130 5600 5110
1.74 26.2 8030 5690 7510 5630 6980 5580 6480 5510 5960 5380
2.04
34.5 8390 5870 7840 5810 7290 5770 6750 5730 6220 5600
1.2
13.6 7750 5140 7240 5570 6670 5670 6140 5530 5650 5430
1.5 20.1 8350 5900 7840 5800 7270 5770 6710 5710 6100 5620
1.8 26.5 8870 6200 8270 6100 7670 6050 7110 6040 6510 6020
2.1
33.7 9270 6490 8650 6370 8030 6310 7390 6270 6800 6250
1.56 21.5 9640 6740 9010 6660 8350 6620 7640 6540 6970 6470
1.92 32.7
10330 7620 9630 7420 8970 7330 8250 7260 7540 6940
2.28
40.7 10900 7840 10160 7790 9410 7720 8650 7610 7940 7310
2.64
54.3 11340 8060 10580 7930 9800 7840 9020 7760 8230 7570
NOTES:
1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN
SPEED MUST MULTIPLY A CORRECTION FACTOR.
2) W.P.D:WATER PRESSURE DROP
TOTAL:TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY
Cooling Capacity Correction Factors:
MODEL
MEDIUM
TOTAL 0.85 0.82 0.84 0.84 0.87 0.85 0.86
SENSIBLE 0.78 0.75 0.78 0.8 0.8 0.8 0.8
LOW
TOTAL 0.66 0.6 0.65 0.65 0.68 0.7 0.71
SENSIBLE 0.58 0.55 0.58 0.6 0.62 0.63 0.66