K
knappfrankNov 25, 2025
How to fix communication problem between thermostat and PCB in McQuay Chiller?
- TTiffany PrinceNov 25, 2025
A communication problem between the thermostat and PCB in your McQuay Chiller can arise from several factors. The communication cable might be connected A/B oppositely, or it could be loose. Interference can also occur if the communication cable and power cable are crossed. Other potential issues include the PCB not being powered on, excessive communication distance, a PCB communication port failure, a thermostat communication port failure, or an incorrect address setting. To troubleshoot: 1. Check the communication cable connection. 2. Re-do the wiring to avoid the power cable and communication cable being close, and use shielded twisted cable. 3. Check the PCB. 4. Use shielded twisted cable and shorten JP7 on the PCB if the communication distance is too long. 5. Check by monitorin...