13
MODEL
WATER
FLOW

W.P.D

ENTERING AIR: DB28ºC, WB21ºC
ENTERING WATER TEMPERATUREºC
6 7 8 9 10
TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE
W W W W W W W W W W

0.24
5.6 2095 1533 1959 1513 1853 1474 1717 1416 1513 1358
0.33 9.7 2357 1727 2241 1678 2095 1668 1940 1639 1785 1591
0.42
14.8 2551 1872 2386 1833 2241 1785 2095 1765 1930 1736
0.51 21.6 2697 1969 2658 1940 2357 1882 2192 1833 2027 1814

0.36 4 3133 2318 2939 2260 2706 2212 2483 2173 2425 2144
0.48 9.2 3482 2561 3259 2512 3036 2483 2803 2444 2716 2396
0.6 13.2 3754 2745 3492 2687 3259 2638 2997 2600 2891 2580
0.72
18.7 3948 2910 3686 2832 3414 2803 3143 2745 3036 2687

0.42
7.3 3938 2871 3676 2803 3453 2745 3182 2706 2774 2648
0.6 13.8 4520 3201 4249 3279 3977 3240 3676 3220 3376 3162
0.78 21.6 4937 3618 4734 3579 4287 3531 3996 3492 3676 3453
0.96 31 5228 3783 4879 3764 4559 3715 4200 3676 3870 3647

0.72
18.7 6305 4588 5907 4549 5500 4501 5034 4433 4598 4278
0.9 32.7 6800 4753 6344 4695 5888 4588 5461 4530 5015 4433
1.08 38.2 7188 5025 6635 4811 6227 4743 5742 4695 5277 4685
1.26
50 7508 5209 6994 5151 6499 5063 5995 5044 5490 4957

1.14 12.5 8381 6169 7867 6072 7265 6004 6528 5878 5956 5733
1.44 18.7 9060 6334 8517 6247 7944 6198 7353 6140 6703 6121
1.74 26.2 9613 6809 8992 6732 8352 6683 7760 6596 7139 6441
2.04
34.5 10049 7023 9390 6965 8730 6906 8080 6868 7450 6703

1.2
13.6 9283 6150 8662 6674 7983 6790 7353 6615 6771 6499
1.5 20.1 10001 7062 9390 6945 8711 6906 8041 6829 7304 6722
1.8 26.5 10612 7430 9904 7304 9186 7246 8517 7236 7789 7207
2.1
33.7 11097 7770 10360 7634 9613 7556 8846 7508 8138 7479

1.56 21.5 11543 8070 10786 7973 10001 7935 9147 7838 8342 7750
1.92 32.7 12377 9128
11533 8885 10748 8769 9884 8701 9031 8313
2.28
40.7 13056 9390 12164 9322 11271 9244 10360 9118 9506 8749
2.64
54.3 13580 9642 12668 9496 11737 9390 10796 9293 9855 9060
NOTES:
1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN
SPEED MUST MULTIPLY A CORRECTION FACTOR.
2) W.P.D:WATER PRESSURE DROP
TOTAL:TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY
Cooling Capacity Correction Factors:
MODEL       
MEDIUM
TOTAL 0.85 0.82 0.84 0.84 0.87 0.85 0.86
SENSIBLE 0.78 0.75 0.78 0.8 0.8 0.8 0.8
LOW
TOTAL 0.66 0.6 0.65 0.65 0.68 0.7 0.71
SENSIBLE 0.58 0.55 0.58 0.6 0.62 0.63 0.66