14
MODEL
WATER
FLOW
W.P.D
ENTERING WATER TEMPERATUREºC
6 7 8 9 10
TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE
W W W W W W W W W W
0.24
5.6 1698 1242 1591 1222 1504 1193 1387 1145 1222 1096
0.33 9.7 1911 1397 1814 1358 1698 1358 1571 1329 1445 1290
0.42
14.8 2066 1523 1930 1484 1814 1445 1698 1436 1562 1407
0.51 21.6 2183 1601 2153 1571 1911 1533 1775 1484 1639 1465
0.36 4 2541 1882 2386 1833 2192 1795 2008 1765 1969 1736
0.48 9.2 2823 2076 2638 2037 2464 2008 2270 1979 2202 1940
0.6 13.2 3036 2231 2832 2173 2638 2144 2425 2105 2338 2086
0.72
18.7 3191 2357 2988 2299 2765 2270 2551 2231 2464 2173
0.42
7.3 3191 2318 2978 2270 2794 2231 2580 2192 2241 2144
0.6 13.8 3657 2590 3444 2658 3220 2629 2978 2609 2735 2561
0.78 21.6 3996 2929 3832 2900 3473 2862 3240 2832 2978 2794
0.96 31 4239 3065 3958 3046 3696 3017 3405 2978 3133 2949
0.72
18.7 5112 3715 4782 3686 4452 3647 4074 3589 3725 3463
0.9 32.7 5510 3851 5141 3802 4763 3715 4423 3667 4064 3589
1.08 38.2 5820 4064 5374 3890 5044 3841 4656 3802 4278 3802
1.26
50 6082 4220 5665 4171 5267 4103 4850 4084 4443 4016
1.14 12.5 6790 4996 6373 4918 5888 4860 5287 4763 4831 4646
1.44 18.7 7343 5131 6897 5063 6431 5025 5956 4976 5432 4957
1.74 26.2 7789 5519 7285 5461 6771 5413 6286 5345 5781 5219
2.04
34.5 8138 5694 7605 5636 7071 5597 6548 5558 6033 5432
1.2
13.6 7518 4986 7023 5403 6470 5500 5956 5364 5481 5267
1.5 20.1 8100 5723 7605 5626 7052 5597 6509 5539 5917 5451
1.8 26.5 8604 6014 8022 5917 7440 5869 6897 5859 6315 5839
2.1
33.7 8992 6295 8391 6179 7789 6121 7168 6082 6596 6063
1.56 21.5 9351 6538 8740 6460 8100 6421 7411 6344 6761 6276
1.92 32.7 10020
7391 9341 7197 8701 7110 8003 7042 7314 6732
2.28
40.7 10573 7605 9855 7556 9128 7488 8391 7382 7702 7091
2.64
54.3 11000 7818 10263 7692 9506 7605 8749 7527 7983 7343
NOTES:
1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN
SPEED MUST MULTIPLY A CORRECTION FACTOR.
2) W.P.D:WATER PRESSURE DROP
TOTAL:TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY
Cooling Capacity Correction Factors:
MODEL
MEDIUM
TOTAL 0.85 0.82 0.84 0.84 0.87 0.85 0.86
SENSIBLE 0.78 0.75 0.78 0.8 0.8 0.8 0.8
LOW
TOTAL 0.66 0.6 0.65 0.65 0.68 0.7 0.71
SENSIBLE 0.58 0.55 0.58 0.6 0.62 0.63 0.66