EasyManuals Logo

McQuay MDS 100B User Manual

McQuay MDS 100B
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
70 Service Manual SM-MDS_(ii)
6.5 Outdoor Error Code for MDS-M PCB
Error
Code
Description
Possible Causes
Page
R22
Wrong combination of
PCB and software
PCB hardware is designed for R22 but software for R410A unit is installed into it.
88
R410
Wrong combination of
PCB and software
PCB hardware is designed for R410A but software for R22 unit is installed into it.
88
ERSE
Wrong dipswitch setting
Outdoor dipswitch setting wrong
Outdoor model dipswitch setting wrong
89
EC00
-
EC47
00# - 47# indoor unit
communication failure
Indoor 00# - 47# and outdoor communication wire broken
Indoor 00# - 47# and outdoor communication wire loose
Indoor 00# - 47# and outdoor communication wire A B reverse
Indoor 00# - 47# and outdoor jump wire not correct, still on update status
Indoor 00# - 47# and outdoor PCB program not compatible
Indoor 00# - 47# and outdoor PCB abnormal
76
ER48
Digital compressor
overload
Digital compressor operating current too high, overload protector OL4 on
77
ER49
Fixed compressor 1
overload
Fixed compressor 1 operating current too high, overload protector OL1 on
ER50
Fixed compressor 2
overload
Fixed compressor 2 operating current too high, overload protector OL2 on
ER51
Fix compressor 3
overload
Fixed compressor 3 operating current too high, overload protector OL3 on
ER52
Discharge pressure too
high
Outdoor motor broken (cooling)
Outdoor circulating air short-circuit (cooling)
Outdoor heat exchanger too dirty (cooling)
Outdoor ball valve not open
Indoor circulating air short-circuit (heating)
Indoor heat exchanger too dirty (heating)
Indoor unit filter blocked by dirt (heating)
Indoor EXV not on properly (heating)
Refrigerant over charged
Outdoor PCB high pressure output port abnormal
Pressure sensor broken
Pressure switch broken
78
ER53
Suction pressure is too
low
Outdoor ball valve not open
Outdoor heat exchanger efficiency too low when heating
Outdoor motor run abnormally when heating
Refrigerant leakage or insufficient
Outdoor PCB low pressure output port abnormal
Low pressure sensor broken
ER54
Outdoor unit’s IC error
Outdoor PCB chip read faultily at the very beginning when power on
Outdoor PCB chip broken
82