EasyManuals Logo

McQuay TGZ 040A User Manual

McQuay TGZ 040A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
OMM TGZ-1 TGZ 040A through TGZ 190A 63
SET UNIT SPs (7)
Ice Time Delay=Xxsec
Clear Ice Delay=No
H.G. Delay = XX sec
H.G. Delay, hot gas bypass delay, keeps the hot gas solenoid valve closed when the first
compressor on a circuit starts. This delay allows sufficient condenser pressure to build up.
The Ice entries do not apply to TGZ units.
SET UNIT SPs (8)
CLOCK
dd/mmm/yyyy
hh:mm:ss
SET UNIT SPs (9)
Units = °
°°
°F/psi
Lang = ENGLISH
Refrig = R134a
Refrigerant type is factory-set.
SET UNIT SPs (10)
Protocol = Modbus
Ident Number=001
Baud Rate=9600
BAS interface settings, available mid-2003.
SET UNIT SPs (11)
Evap Press Sensor
Cir 1 Cir 2 Offset
00.0 00.0 (psi)
The pressure offsets on menus 8 and 9 and the temperature offsets on menus 10, 11 and 12
correct the controller's display. The sensors used in these units have a high degree of
repeatability but may need correction (offset). An accurate pressure gauge or thermometer
is used to determine the correct temperature or pressure. A positive or negative offset value
is then entered to make the controller reading agree with the measured value.
SET UNIT SPs (12)
Cond Press Sensor
Cir 1 Cir 2 Offset
00.0 00.0 (psi)
SET UNIT SPs (13)
LWT Sensors
Evap offset= 00.0°
°°
°F
Cond Offset= 00.0
o
F
SET UNIT SPs (14)
EWT Sensors
Evap offset= 00.0°
°°
°F
Cond Offset= 00.0
o
F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay TGZ 040A and is the answer not in the manual?

McQuay TGZ 040A Specifications

General IconGeneral
BrandMcQuay
ModelTGZ 040A
CategoryWater Heater
LanguageEnglish