OMM TGZ-1 TGZ 040A through TGZ 190A 63
SET UNIT SPs (7)
Ice Time Delay=Xxsec
Clear Ice Delay=No
H.G. Delay = XX sec
H.G. Delay, hot gas bypass delay, keeps the hot gas solenoid valve closed when the first
compressor on a circuit starts. This delay allows sufficient condenser pressure to build up.
The Ice entries do not apply to TGZ units.
SET UNIT SPs (8)
CLOCK
dd/mmm/yyyy
hh:mm:ss
SET UNIT SPs (9)
Units = °
°°
°F/psi
Lang = ENGLISH
Refrig = R134a
Refrigerant type is factory-set.
SET UNIT SPs (10)
Protocol = Modbus
Ident Number=001
Baud Rate=9600
BAS interface settings, available mid-2003.
SET UNIT SPs (11)
Evap Press Sensor
Cir 1 Cir 2 Offset
00.0 00.0 (psi)
The pressure offsets on menus 8 and 9 and the temperature offsets on menus 10, 11 and 12
correct the controller's display. The sensors used in these units have a high degree of
repeatability but may need correction (offset). An accurate pressure gauge or thermometer
is used to determine the correct temperature or pressure. A positive or negative offset value
is then entered to make the controller reading agree with the measured value.
SET UNIT SPs (12)
Cond Press Sensor
Cir 1 Cir 2 Offset
00.0 00.0 (psi)
SET UNIT SPs (13)
LWT Sensors
Evap offset= 00.0°
°°
°F
Cond Offset= 00.0
o
F
SET UNIT SPs (14)
EWT Sensors
Evap offset= 00.0°
°°
°F
Cond Offset= 00.0
o
F