OMM TGZ-1 TGZ 040A through TGZ 190A 7
TGZ Electrical Data
Table 1, Compressor Amp Draw
STANDARD UNIT W/O EXT. OL'S
RATED LOAD
AMPS
OPTIONAL UNIT WITH EXT. OL'S
RATED LOAD AMPS (SEE
NOTE 1)
LOCKED ROTOR AMPS
COMPRESSORS
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
TGZ
UNIT
SIZE
VOLTS
FREQ.
(HERTZ)
No.1
No.3
No.5
No.2
No.4 No.6
No.1
No.3
No.5
No.2
No.4
No.6
No.1
No.3
No.5
No.2
No.4
No.6
208 35.3
35.3
- 35.3
35.3 - 30.8
30.8
- 30.8
30.8
- 239 239
- 239 239
-
230 35.3
35.3
- 35.3
35.3 - 28.0
28.0
- 28.0
28.0
- 239 239
- 239 239
-
460 17.9
17.9
- 17.9
17.9 - 14.0
14.0
- 14.0
14.0
- 125 125
- 125 125
-
040
575
60
11.5
11.5
- 11.5
11.5 - 11.2
11.2
- 11.2
11.2
- 80 80 - 80 80 -
208 48.1
48.1
- 48.1
48.1 - 42.0
42.0
- 42.0
42.0
- 300 300
- 300 300
-
230 48.1
48.1
- 48.1
48.1 - 38.4
38.4
- 38.4
38.4
- 300 300
- 300 300
-
460 21.8
21.8
- 21.8
21.8 - 19.2
19.2
- 19.2
19.2
- 150 150
- 150 150
-
050
575
60
19.9
19.9
- 19.9
19.9 - 15.2
15.2
- 15.2
15.2
- 109 109
- 109 109
-
208 54.0
54.0
- 54.0
54.0 - 54.0
54.0
- 54.0
54.0
- 340 340
- 340 340
-
230 52.6
52.6
- 52.6
52.6 - 48.8
48.8
- 48.8
48.8
- 340 340
- 340 340
-
460 25.6
25.6
- 25.6
25.6 - 24.4
24.4
- 24.4
24.4
- 173 173
- 173 173
-
060
575
60
21.2
21.2
- 21.2
21.2 - 19.6
19.6
- 19.6
19.6
- 132 132
- 132 132
-
208 73.1
73.1
- 73.1
73.1 - 58.0
58.0
- 58.0
58.0
- 505 505
- 505 505
-
230 73.1
73.1
- 73.1
73.1 - 52.8
52.8
- 52.8
52.8
- 505 505
- 505 505
-
460 30.1
30.1
- 30.1
30.1 - 26.4
26.4
- 26.4
26.4
- 225 225
- 225 225
-
080
575
60
24.4
24.4
- 24.4
24.4 - 21.2
21.2
- 21.2
21.2
- 180 180
- 180 180
-
208 73.1
73.1
- 73.1
73.1 - 69.2
69.2
- 69.2
69.2
- 500 500
- 500 500
-
230 73.1
73.1
- 73.1
73.1 - 62.4
62.4
- 62.4
62.4
- 500 500
- 500 500
-
460 35.3
35.3
- 35.3
35.3 - 31.2
31.2
- 31.2
31.2
- 250 250
- 250 250
-
100
575
60
28.2
28.2
- 28.2
28.2 - 25.2
25.2
- 25.2
25.2
- 198 198
- 198 198
-
208 73.1
73.1
- 93.6
93.6 - 69.2
69.2
- 88.8
88.8
- 500 500
- 599 599
-
230 73.1
73.1
- 93.6
93.6 - 62.4
62.4
- 80.0
80.0
- 500 500
- 599 599
-
460 35.3
35.3
- 45.5
45.5 - 31.2
31.2
- 40.0
40.0
- 250 250
- 310 310
-
110
575
60
28.2
28.2
- 36.5
36.5 - 25.2
25.2
- 32.0
32.0
- 198 198
- 239 239
-
208 93.6
93.6
- 93.6
93.6 - 88.8
88.8
- 88.8
88.8
- 599 599
- 599 599
-
230 93.6
93.6
- 93.6
93.6 - 80.0
80.0
- 80.0
80.0
- 599 599
- 599 599
-
460 45.5
45.5
- 45.5
45.5 - 40.0
40.0
- 40.0
40.0
- 310 310
- 310 310
-
120
575
60
36.5
36.5
- 36.5
36.5 - 32.0
32.0
- 32.0
32.0
- 239 239
- 239 239
-
208 73.1
73.1
73.1
73.1
73.1 73.1
69.2
69.2
69.2
69.2
69.2
69.2
500 500
500 500 500
500
230 73.1
73.1
73.1
73.1
73.1 73.1
62.4
62.4
62.4
62.4
62.4
62.4
500 500
500 500 500
500
460 35.3
35.3
35.3
35.3
35.3 35.3
31.2
31.2
31.2
31.2
31.2
31.2
250 250
250 250 250
250
150
575
60
28.2
28.2
28.2
28.2
28.2 28.2
25.2
25.2
25.2
25.2
25.2
25.2
198 198
198 198 198
198
208 73.1
73.1
73.1
93.6
93.6 93.6
69.2
69.2
69.2
88.8
88.8
88.8
500 500
500 599 599
599
230 73.1
73.1
73.1
93.6
93.6 93.6
62.4
62.4
62.4
80.0
80.0
80.0
500 500
500 599 599
599
460 35.3
35.3
35.3
45.5
45.5 45.5
31.2
31.2
31.2
40.0
40.0
40.0
250 250
250 310 310
310
170
575
60
28.2
28.2
28.2
36.5
36.5 36.5
25.2
25.2
25.2
32.0
32.0
32.0
198 198
198 239 239
239
208 93.6
93.6
93.6
93.6
93.6 93.6
88.8
88.8
88.8
88.8
88.8
88.8
599 599
599 599 599
599
230 93.6
93.6
93.6
93.6
93.6 93.6
80.0
80.0
80.0
80.0
80.0
80.0
599 599
599 599 599
599
460 45.5
45.5
45.5
45.5
45.5 45.5
40.0
40.0
40.0
40.0
40.0
40.0
310 310
310 310 310
310
190
575
60
36.5
36.5
36.5
36.5
36.5 36.5
32.0
32.0
32.0
32.0
32.0
32.0
239 239
239 239 239
239
NOTES:
1. External overloads only available on Templifier units with 140°F maximum condenser leaving water temperature.
2. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control
transformer.
3. Single point power supply requires a single fused disconnect to supply electrical power to the unit.
4. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.