8 TGZ 040A through TGZ 190A OMM TGZ-1
Table 2, Wire Sizing Amps, Standard Multi-Point Power Supply
MINIMUM CIRCUIT AMPACITY (MCA) POWER SUPPLY
WITHOUT EXTTERNAL
OVERLOADS
WITH EXTERNAL
OVERLOADS
WITHOUT EXTERNAL
OVERLOADS
WITH EXTERNAL
OVERLOADS
MULTIPLE POINT POWER SUPPLY
WIRE GAUGE
75
°
°°
°
C
WIRE GAUGE
75
°
°°
°
C
TGZ
UNIT
SIZE
VOLTS
FREQ.
(HERTZ)
CIRCUIT
NO.1
CIRCUIT
NO.2
CIRCUIT
NO.1
CIRCUIT
NO.2
FIELD
WIRE
QTY.
CIRCUIT
NO.1
CIRCUIT
NO.2
FIELD
WIRE
QTY.
CIRCUIT
NO.1
CIRCUIT
NO.2
208 79 79 69 69 3 #4 #4 3 #4 #4
230 79 79 63 63 3 #4 #4 3 #6 #6
460 40 40 32 32 3 #8 #8 3 #10 #10
040
575
60
26 26 25 25 3 #10 #10 3 #10 #10
208 108 108 95 95 3 #2 #2 3 #3 #3
230 108 108 86 86 3 #2 #2 3 #3 #3
460 49 49 43 43 3 #8 #8 3 #8 #8
050
575
60
45 45 34 34 3 #8 #8 3 #10 #10
208 122 122 122 122 3 #1 #1 3 #1 #1
230 118 118 110 110 3 #1 #1 3 #2 #2
460 58 58 55 55 3 #6 #6 3 #6 #6
060
575
60
48 48 44 44 3 #8 #8 3 #8 #8
208 165 165 131 131 3 2/0 2/0 3 1/0 1/0
230 165 165 119 119 3 2/0 2/0 3 #1 #1
460 68 68 59 59 3 #4 #4 3 #6 #6
080
575
60
55 55 48 48 3 #6 #6 3 #8 #8
208 165 165 156 156 3 2/0 2/0 3 2/0 2/0
230 165 165 140 140 3 2/0 2/0 3 1/0 1/0
460 79 79 70 70 3 #4 #4 3 #4 #4
100
575
60
64 64 57 57 3 #6 #6 3 #6 #6
208 165 211 156 200 3 2/0 4/0 3 2/0 3/0
230 165 211 140 180 3 2/0 4/0 3 1/0 3/0
460 79 102 70 90 3 #4 #2 3 #4 #3
110
575
60
64 82 57 72 3 #6 #4 3 #6 #4
208 211 211 200 200 3 4/0 4/0 3 3/0 3/0
230 211 211 180 180 3 4/0 4/0 3 3/0 3/0
460 102 102 90 90 3 #2 #2 3 #3 #3
120
575
60
82 82 72 72 3 #4 #4 3 #4 #4
208 238 238 225 225 3 250 250 3 4/0 4/0
230 238 238 203 203 3 250 250 3 4/0 4/0
460 115 115 101 101 3 #2 #2 3 #2 #2
150
575
60
92 92 82 82 3 #3 #3 3 #4 #4
208 238 304 225 289 3 250 350 3 4/0 350
230 238 304 203 260 3 250 350 3 4/0 300
460 115 148 101 130 3 #2 1/0 3 #2 #1
170
575
60
92 119 82 104 3 #3 #1 3 #4 #2
208 304 304 289 289 3 350 350 3 350 350
230 304 304 260 260 3 350 350 3 300 300
460 148 148 130 130 3 1/0 1/0 3 #1 #1
190
575
60
119 119 104 104 3 #1 #1 3 #2 #2
NOTES:
1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of the other compressor RLA's.
2. Multiple point power supply requires a separate fused disconnect for each circuit to supply electrical power to the unit.
3. External compressor overload option is only available for units with 140° F maximum leaving condenser water temperature.
4. Wire sizes shown above are for standard ambient temperature and short runs of wire.